Mode
1.10
1.11
3.10
3.11
3.20
3.21
User Setting
Parameter
Factory setting
K1
OFF
OFF
OFF
OFF
OFF
OFF
K2
ON
ON
ON
ON
ON
ON
MODBUS Slave
Bus Address
247
247
247
247
247
247
Addressing
OFF
OFF
OFF
OFF
OFF
OFF
UART Baudrate
19200
19200
19200
19200
19200
19200
UART Mode
8E1
8E1
8E1
8E1
8E1
8E1
1
For adjustment "Setting Sep" > 0 (
Base setup)
2
For control circuit 1 in operation with a second control circuit (
Base Setup / Function E2)
3
For control circuit 2 in operation with a second control circuit (presetting depending on programmed function)
4
In operation with control circuit 2 and programmed function 15 D for digital input (
IO Setup)
5
In operation with control circuit 2 and programmed function 16 D for digital input (
IO Setup)
6
IO option Add-on module type Z-Modul-B
10.2
Possible allocation of the IOs, PINs
Units for analog inputs E1 and E2
The following units can be set for programmed sensors with free measuring range (0 - 10 V, 0 - 20 mA, 4 -
20 mA).
E1 Analog In
E2 Analog In
°
C, m
3
/h, bar, %, Pa, m/s, m
3
/s, Ohm, mbr,
°
F, ft/s, cfm, in.wg, psi, ppm
Analog outputs A / A2
Function
Description function A / A2
OFF
No function
Constant voltage 10 V
(1A)
Constant v10 V (factory setting)
1st control signal
(2A)
Proportional modulation (control circuit 1)
E1
(3A)
proportional input E1
E2
(4A)
proportional input E2
Group2
(5A)
Group control (
Controller Setup - group 2)
2.Cooling
(6A)
Only in mode
2.03
temperature controller with additional functions (not for Z-Module-
B).
Controller output 2 with rising activation at Actual>Nominal =
Cool
.
2.Heating
(7A)
Only in mode
2.03
temperature controller with additional functions (not for Z-Module-
B).
Controller output 2 with rising activation at Actual<Nominal =
Heat
.
2. control signal
(8A)
Controlled 0 - 10 V output for control circuit 2 (factory setting for
“
A1
”
at operation
with second control circuit).
Output frequency
(9A)
Proportional to the output frequency
Group1
(10A)
Group control (
Controller Setup - group 1)
Group3
(12A)
Group control (
Controller Setup - group 3)
Operating Instructions
Fcontrol
–
model series FKDM25/32AM-C
Menu tables
L-BAL-E214-GB 1446 Index 002
Part.-No.
84/99