8.2
Procedure for commissioning
Sequence
Setting
1
"
Check if Thermostats or Thermistors of the motor are connected to input
“
TB/TP In
”
.
"
If the motor protection function of the device is not neccesary the both terminals
“
TB / TP
”
have to be bridged.
2
Check if contact for enable is conected to
“
Digital In 1
”
.
If the device remote control is not required, the two terminals
“
D1 / D1
”
must be bridged (alternative reprogram
D1 function
IO Setup / Digital inputs
“
D1
”
/
“
D2
”
).
3
"
Check connection and close housing carefully.
4
"
Turn on mains voltage.
Display after
fi
rst turning on the mains voltage
5
Information
In the menu group
Start
the adjustment for
Motor
is
OFF
for factory setting => display:
|
STOP
|
.
This prevents the system from inadvertently starting up before con
fi
guration is complete.
Switch over via
|
Menu
|
to Main menue
6
Menu group:
Start
"
Set the menu language if necessary (factory setting English = Language GB).
"
The display can be switched between SI units (US units = OFF) and imperial (US) units (US units = ON).
7
Menu group:
Base setup
"
Setting the desired operation Mode (factory setting
1.10
=
Speed controller maximal output
frequency 50 Hz
selection Mode).
"
Further settings depend on the selected mode and the sensor / setting signal used.
Attention!
When saving the operating mode, the respective preset factory operating-mode setting is loaded. That means,
the settings you have made, e.g., in
“
Motor Setup
”
are lost. An exception: the menu language setting remains
preserved.
8
Menu group:
Motor Setup
Make further settings depending on the connected motor.
9
Menu group
Setting
:
"
Set the parameters for the control operation
10
Menu group
Start
:
"
Switch setting for
Motor
to
ON
.
Information
Settings for U/f characteristic can only be made when no motor modulation is present! This is the
same also for the setting of Mode.