For operation as controller (starting from
3.10
): switch over
“
Setpoint 1
”
/
“
external Setpoint
”
Possible only for operation with one control circuit!
Under Base setup
“
E2 function
”
programmed to function
|
1E
|
for
“
external setpoint
”
.
Contact at digital input e.g.
“
Digital In 1
”
=
“
D1
”
-
“
D1
”
Controller
D1 D1
1
0
n = 0 – 100 %
- - - - -
Se
ES
E2
27.11.2008
v_6d_sollwert1_externer_sollwert_m.vsd
1
M
1
Setting
“
Setpoint1
”
ES
External Setpoint e.g. 5 V
Se
Sensor
•
“
D1 Inverting
”
=
“
ON
”
: Setting at the unit at
opened contact / Signal Extern at closed
contact
•
“
D1 Inverting
”
=
“
OFF
”
: Setting at the unit at
closed contact / Signal Extern at opened
contact
9.6.2.8
Automatic control / speed manual Function
|
7D
|
(mode
3.10
)
Factory setting for digital input
“
D2
”
.
Switch over between automatic control to set target value (depending on the activation:
“
Setpoint1
”
,
“
Setpoint2
”
) and the default for
“
manual operation
”
set at the device.
If for input 2
“
E2 Function
”
the function is programmed to
|
2E
|
switch over between
“
Setpoint 1
”
or
“
Setpoint 2
”
and external Manual mode.
With activated manual mode the value
“
Set external2
”
is displayed in menu group
“
Info
”
.
Contact at digital input e.g.
“
Digital In 1
”
Controller
D2 D2
1
0
n = 0 -100 %
1
n = 80 %
0
- - - - -
- - - - -
- - - - -
Se
E1
ES
E2
17.10.2014
v_7d_regelung_hand_m_d2.vsd
3
2
1
M
1
Setting
“
Setpoint1
”
2
Setting
“
Setpoint2
”
3
Setting
“
Speed manual
”
EH
Signal for Manual mode extern, E2 Function =
|
2E
|
Se
Sensor
•
“
D2 Inverting
”
=
“
OFF
”
Automatic control at
opened contact / manual operation at closed
contact.
•
“
D2 Inverting
”
=
“
ON
”
: Automatic control at
closed contact / manual operation at opened
contact.
Possible only for operation with one control circuit!
9.6.2.9
Reverse action of control function (
2.01
), Function
|
8D
|
Switchover between: Increasing modulation during increasing actual-value and increasing modulation
during sinking actual-value.
The factory presets for the
“
Control function
”
are dependent on the selected mode of operation (
Controller Setup - reverse operation of the control function).
When switching over via a digital input, the device works with the opposite function as set there.
The inversion of the control function in
fl
uences both circuits in operation with two control circuits.
Controller Setup
Settings in Controller Setup
Display for operation with two control circuits:
“
1. Actual>Set=n
”
for control circuit 1
“
2. Actual>Set=n
”
for control circuit 2
ON
Val>Set=n+
Operating Instructions
Fcontrol
–
model series FKDM25/32AM-C
Programming
L-BAL-E214-GB 1446 Index 002
Part.-No.
52/99