9.5.9
Group control
9.5.9.1
Group version
Groups can be controlled by the analogue output
“
A
”
or the relay outputs
“
K1
”
and
“
K2
”
.
Controller Setup
Following group versions are available:
0
: One controlled group and up to three switched groups (factory setting)
1
: Two controlled groups
0
Group version
Information
•
The groups must be connected at the appropriate programmed output when activating by the
analogue outputs and relays.
•
The assignment of the analogue outputs and the relays for the group control takes place in the IO
Setup.
•
The number of possible groups depends on the available hardware outputs.
9.5.9.2
Group variant 0: One controlled group and up to three switched groups
Control group 2/3/4 via relais
Controller Setup
Group 2 ON value
Switch-on value for Group2
Setting range: 0 - 100 %
Factory setting: 50 % *
50 %
Group 2 ON value
Controller Setup
OFF Value Group2
Switch-off value for group2
Setting range: 0 - 100 %
Factory setting: 45 % *
45 %
OFF Value Group2
Controller Setup
nmin at Group2
Minimum Value for Group2
Setting range: 0 - 100 %
Factory setting: 20 % *
20 %
nmin at Group2
Controller Setup
Group 3 ON value
Switch-on value for Group3
Setting range: 0 - 100 %
Factory setting: 70 % *
70 %
Group 3 ON value
Controller Setup
OFF Value Group3
Switch-off value for group3
Setting range: 0 - 100 %
Factory setting: 65 *
65 %
OFF Value Group3
Controller Setup
nmin at Group3
Minimum Value for Group3
Setting range: 0 - 100 %
Factory setting: 30 % *
30 %
nmin at Group
3
Operating Instructions
Fcontrol
–
model series FKDM25/32AM-C
Programming
L-BAL-E214-GB 1446 Index 002
Part.-No.
42/99