Setting
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (display as long as no allocation is carried
out:
|
- - - - -
|
IO Setup).
- - - - -
Setpoint2
Setting
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
3.10
and
3.11
Setting range: in measuring range of sensor
Factory setting: 3.0 bar
3.20
and
3.21
Setting range: dependent on the selected refrigerant
Factory setting: 5.0 K
3.00 bar
Pband
Setting
Min. Speed
Setting range:
|
OFF
|
→
“
Shutdown Freq.
”
(
Motor Setup) -
“
Max. Speed
”
.
Mode
3.10
and
3.20
= 25.0 Hz
Mode
3.11
and
3.21
= 30.0 Hz
25.0 Hz
Min. Speed
Setting
Max. Speed
Setting range:
“
Max. Frequency
”
(
Motor Setup) -
“
Min. Speed
”
Factory setting:
Mode
3.10
and
3.20
= 50.0 Hz
Mode
3.11
and
3.21
= 87.0 Hz
50.0 Hz
Max. Speed
Setting
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
The manual mode only becomes active if the function
|
2E
|
“
Ext. manual mode
”
was
deactivated
fi
rst
Basic setting.
OFF
Manual mode
Setting
Speed Manual mode
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...
“
Max. Frequency
”
(
Motor Setup)
Factory setting: 50.0 Hz
50.0 Hz
Speed man.
Switch over: Regulation via sensor on
“
E1
”
/ speed Manual mode via signal on
“
E2
”
With activated manual mode the value
“
Set external2
”
is displayed in menu group
“
Info
”
.
Info
Display for
“
Set external2
”
in menu group Info
Info
- - - - -
Set external2
57 %
Set external2
Control to sensor on
“
E1
”
and set target value.
External Manual mode ac-
tive = signal on
“
E2
”
.
Operating Instructions
Fcontrol
–
model series FKDM25/32AM-C
Programming
L-BAL-E214-GB 1446 Index 002
Part.-No.
32/99