7.5
|
Installation
|
Heating 2
◄
Heating2
↑
|
ESC
|
P
↓
H2 Mode
H2 Mode
OFF
= heater inactive
(at factory)
1
= Heating works as a two-point controller via relay
2
= Heating works as a proportional controller (0 - 10 V)
3
= piglet nest heating (
following chapter)
4
= piglet nest heating (Blaffert only P-controller)
H2 Input
H2 Input
0
= Sensor on E1 = Control via offset to setpoint ventilation
(factory setting)
1
= Sensor on E2 = Control independent from the ventilation nominal value
2
= Sensor value via bus from
“
master
”
independently of ventilation setpoint
3
= sensor at E3 = regulation independent of ventilation setpoint (only possible of not
usedas a digital input, internal jumper
“
J2
”
must be pluggedto the right =
“
E3
”
.
H2 Val<Set=+
H2 Val<Set=+
Basic control function:
OFF
= cooling
ON
= heating
(factory setting)
7.5.1
Special function for
“
piglet nest warm water heating
”
This function regulates the start-up temperature for a hot water heating plate to exactly the desired
setpoint.
Tips:
The function is part of heating circuit 2 of the device.
For this function
“
H2 Mode
”
must be set to
“
3
”
.
The input for
“
H2
”
must be assignedthe temperature source 2 (sensor at E2).
The control range of the heater 2 shouldbe
“
5 K
”
with this function (setting in the main menu
“
Heating
”
).
The greater the control range is set, the gentler the control behaviour. If no stable start-up temperature
is reached, the control algorithm must be adjusted. The parameters: H2, KP, KI, KD and TI are
responsible for this. The displayed values are reference values from similar applications. If the
regulator is unstable, the parameter
“
H2 TI
”
can be increased
rst (e.g. by 2 - 3 points). This serves to
slow down the integration behaviour, i.e. the regulator responds a little slower which normally results
in more stability.
The function andposition of the start-up temperature is very important for a goodregulation. The
sensor must be installed directly behind the mixer valve. This rules out disturbance variables and
enables maximum response behaviour (short controlledmember).
Blaffertconst.
Blaffertconst.
Adjustment range: 0.0 - 10.0
Factory setting: 2.9
H2 KP
H2 KP
Setting range: 0 - 200 %
Factory setting: 100 %
H2 KI
H2 KI
Setting range: 0 - 200 %
Factory setting: 1 %
H2 KD
H2 KD
Setting range: 0 - 200 %
Factory setting: 100 %
Operating Instructions
UNIcon / Acontrol
The Installation menu
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB