Version
Version
Displays the software version
00056:46:13
O
= Operation,
T
= Time,
C
= Controller
The time counting runs, as soon as mains voltage is connected(without fault).
If events step on (Motor fault, External Error, etc.), the periodof operation is storedat
this time (
Events).
00056:46:13
O
= Operation,
T
= Time,
M
= Motor
The time counting runs as soon as a modulation of the controller is present.
9.3 Setting Ventilation
Ventilation
Ventilation
The ventilation level control is additionally to the bargraph displayed here in digits for
informational purposes.
↑
|
ESC
|
P
↓
9.3.1
For Control of Ventilation
•
In single exhaust air systems direct regulation of the fans in the stall
•
In central exhaust air systems regulation by ventilation shutters
Setpoint
Setpoint
setting range: 0...40.0
°
C
Factory setting: 20.0
°
C
Pband
Pband
Adapting the control action to the system conditions.
small control range = short control times
big control range = longer control times and(higher controller stability)
Setting range: 2.0...20.0 K
Factory setting: 4.0 K
Min. ventilation
Min. ventilation
Setting range: OFF - 6...100 %
Factory setting: 20 %
“
Min. ventilation
”
is greater than setting
“
Max. ventilation
”
Max. ventilation
Max. ventilation
Setting range: 100...50 %
Factory setting: 100 %
Information
With growth program switchedon, the
“
setpoint
”
,
“
Min. ventilation
”
and
“
Max. ventilation
”
is calculated
by the growth program (
growth program).
Settings of these functions under
“
Ventilation
”
are then not possible! Display:
|
- - - - -
|
Operating Instructions
UNIcon / Acontrol
Settings for operation
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
49/83