Ventilation link
Ventilation link
Setting: OFF
–
100 %
At recommended setting 30 %
Lü
ftu
ng
/
Ve
nti
lat
ion
D
ro
ss
e
lk
la
p
p
e
/
th
ro
tt
le
sh
u
tt
e
r
01.10.2008
v_messvent_ventkopp.VSD
1
2
1 Throttle shutter
2 Ventilation
Ventilation
Now the current volume
ow in
“
m
3
/h
³ ”
is displayed instead of ventilation in
“
%
”
on
selecting the Ventilation menu group.
3. Step: Volume
ow at 100 % ventilation
Air volume 100%
Air volume 100%
(Menu: Installation -> Measuring fan)
Setting: Volume
ow which is to be conveyedat 100 % ventilation
Info: Take the design of the ventilation system into consideration
4. Step: Measuring fan properties
Pulse per 1/min
Pulse per 1/min
Menu: Installation -> Measuring fan -> pulse per 1/min
Setting: Number of pulse per 1 rotation e.g. 4
Info: Depending on the measuring fan type, see measuring fan data
Ref. Speed
Ref. Speed
Setting: Speedspeci
cation for a volume
ow of the measuring fan
Info: Depending on the measuring fan type, see measuring fan data
Ref. air volume
Ref. air volume
Setting: Volume
ow speci
cation for the reference speedof the measuring fan
Info: Depending on the measuring fan type, see measuring fan data
Ref. number
Ref. number
Setting: Number of fans for the volume
ow calculation
Info: If several fans are operatedon the device the volume
ow is only measuredon a
fan andthen calculatedby the number of fans of the total volume
ow.
Operating Instructions
UNIcon / Acontrol
The Installation menu
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
45/83