5.7 Control output A1, A2, A3 (0 - 10 V) and PWM
The devices have
three
0 - 10 V outputs andone PWM output (alternative use as a further 0...10 V
output).
It is not permissible to connect outputs of several devices to each other!
The following functions are pre-programmed at the factory (other functions can be assigned in
the IO Setup):
0 - 10 V Output:
•
Output 1
: terminals
“
A1
”
/
“
GND
”
(I
max
10 mA). For ETAvent fans with 0 - 10 V signal or exhaust
air dampers in the compartment (IO Setup: A1 function =
“
0
”
→
ventilation)
•
Output 2
: Terminals
“
A2
”
/
“
GND
”
(I
max
10 mA). Regulator 2 e.g. for throttle shutter after the
exhaust air fan in the stall (IO Setup: A2 function =
“
2
”
→
shutter) factory inverted(10 V...0 V)
i.e.: 10 V = shutter CLOSED, 0 V = shutter OPEN
•
Output 3
: Terminals
“
A3
”
/
“
GND
”
(I
max
10 mA). For Heating (IO Setup: A3 function =
“
1
”
→
Heating )
PWM output alternatively 0 - 10 V
•
Output PWM
: terminals PWM / +24V. For ETAvent fans with PWM input (IO Setup: PWM
function =
“
0
”
→
ventilation)
•
To change to 0 - 10 V output plug internal jumper
“
J1
”
at the top!
Information
Inverting outputs andsetting curve points possible (e.g. for not linear ouput) in IO Setup ( Installation
menu).
5.8 Voltage supply for external devices (+24V, GND)
There is an integratedpower supply for external devices, e.g. a sensor. Te24 V, output voltage
tol/- 20%. max. loadcurrent
Technical data.
It is not permissible to connect outputs of several devices to each other!
In case of overloador short circuit (24 V
–
GND), the external power supply is shut down (multi-fuse).
The device performs a
“
Reset
”
andcontinues operation.
5.9 Relay outputs (K1, K2, K3)
The device has
three
relay outputs, the following functions are pre-programmed
at the factory
. Other
functions can be assignedin
“
IO Setup
”
. Max. contact load5A / 250 V AC.
K1: Fault indication
•
Connection of the
oating contacts to the terminals 11, 12, 14.
•
For operation the relay is energizedi.e. terminals
“
12
”
and
“
14
”
are bridged (factory setting not
inverted).
•
With power failure, internal fuse failure, temperature malfunction or fan error, the error message
relay at the corresponding control unit of the compartment drops, the terminals
“
12
”
and
“
11
”
are
bridged. The
“
Master
”
unit identi
es a malfunction of a network user via the data link, i. e., if a
network user displays a malfunction, the error relay in the master unit also drops. Due to this
function the fault relay of the
“
Slave
”
devices can be assigned if necessary different functions.
•
The fault message via the relay can be acknowledged with the
“
ESC
”
key. If the fault persists
(e.g. sensor break) a message is receivedagain after the adjustable time span
“
Alarm Pause
”
(factory setting 60 minutes).
The error message is not to be layedin the same cable as the bus line.
K2: Heating
•
Connection of the
oating contacts to the terminals 21, 22, 24.
K3: Peak load fan
•
Factory setting relay
“
K3
”
for function
“
peak loadfan
”
assigned(
“
Installation
”
-
“
IO Setup
”
).
A secondfan can be switchedon via the terminals
“
31
”
und
“
32
”
.The activation must be made in
“
Installation
”
-
“
Ventilation
”
(peak load).
Information
Inverting relay function in IO Setup(
menu installation) possible.