7.2.1
Exhaustair rate
Exhaustair rate
Exhaustair rate
Percentage share of the stall in the total exhaust air system.
In central exhaust air systems the total exhaust air is determined from the sum of the
exhaust air percentages of all stalls.
This setting is possible for information in all single exhaust air systems. The exhaust air
total of the system is displayed in the Quickinfo menu.
Adjustment range: 0.0 - 100.0 %
Factory setting: 10.0 %
7.2.2
Minimum speed cut off
Msco.
Msco.
In some cases in which minimum air ventilation is not needed, this feature can
be usedto prevent an undercooling of the room.
Msco. = OFF
(factory setting).
•
If no
“
Min. ventilation
”
is set, the fan comes to a standstill on reaching
the setpoint, the shutter is fully closedin central exhaust air systems.
•
If a
“
Min. ventilation
”
is set (e.g. 20 %), the fan is not switchedoff, the
shutter is never completely closedin central exhaust air systems, i.e. a
minimum ventilation is always ensured(fan does not fall below the
“
Min.
ventilation
”
setting).
MSCO value
For
“
Msco = On
”
takes place a disconnection from setting
“
Min. ventilation
”
to
“
0
”
, if the given difference is reached related to the Setpoint.
•
At a plus value (+) before reaching the desired value
•
At a minus value (-) after falling below the desired value.
•
Setting range: -10...+10 K
•
Factory setting: -5.0 K
Msco
MSCO value