9.
Setting of the Dosing Quantity
The adjustment screw in the quantity adjustment valve must be turned until the floater
upper edge has reached the desired quantity in liters/hour at the scale of the flow
measuring tube (see Diagram 7, Page 15).
For further information, see Section 8 Commissioning.
Diagram 16
The contact maker switches off the device as soon as the floater lowers itself (safety circuit).
At very small quantities, ensure that the floater is still able to lower, otherwise there is a risk that
the floater can not switch off although the flow rate has decreased to zero (risk of insufficient
dosage!!!).
At the standard device, the marking (scaling) at the flow measuring tube is 40
– 400 l/h. As the
function of the automatic shutoff can no longer be warranted for in the lowest range, there is the
option to insert a scaling of 15
– 150 l/h (see Spare Parts List, Page 23, Item 19).
Floater Upper Edge
Flow Measuring
Tube with Scale
Quantity Adjustment
Valve
Summary of Contents for PKT 452
Page 2: ......
Page 4: ......
Page 13: ...Abb 4 Kontaktnehmer Kontaktnehmer Mitte Schwimmeroberkante Kontaktgeber ...
Page 22: ...22 b Bildliche Darstellung des Schaltkastens Abb 9 K 3 K 1 K 2 ...
Page 25: ...25 Bild 1 7 8 50 5 10 6 4 4 3 11 13 Bild 2 9 12 7 8 27 ...
Page 26: ...26 Bild 3 Bild 4 15 13 11 4 9 10 14 4 4 7 6 9 ...
Page 31: ......
Page 34: ...34 ...
Page 36: ...36 ...
Page 45: ...45 Diagram 13 Contact Maker Contact Maker Center Cwenter Floater Upper Edge Contact Maker ...
Page 54: ...54 b Graphic Presentation of the Control Box Diagram 18 K 3 K 1 K 2 ...
Page 57: ...57 Image 1 7 8 50 5 10 6 4 4 3 11 13 Image 2 9 12 7 8 27 ...
Page 58: ...58 Image 3 Image 4 15 13 11 4 9 10 14 4 4 7 6 9 ...
Page 63: ...63 ...