KLIC-SG
Technical Support:
32
ANNEX I. COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a
particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Byte
I/O
C R W T U
DPT_SceneControl
0-63; 128-191
[AC] Scene
0 - 63 (Execute 1 - 64); 128 - 129
(Save 1 - 64)
2
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] On/Off
0 = Off; 1 = On
3
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] On/Off (Status)
0 = Off; 1 = On
4
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[AC] Temperature Setpoint
[16 ... 30] ºC
5
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[AC] Temperature Setpoint (Status)
[16 ... 30] ºC
6
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[AC] Temperature Setpoint: Lower Limit
[16 ... 30] ºC
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[EHS] Water Temperature: Lower Limit
(Status)
[5 ... 55] ºC
7
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[AC] Temperature Setpoint: Lower Limit
(Status)
[16 ... 30] ºC
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[EHS] Water Temperature: Lower Limit
[5 ... 55] ºC
8
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[AC] Temperature Setpoint: Upper Limit
[16 ... 30] ºC
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[EHS] Water Temperature: Upper Limit
[5 ... 55] ºC
9
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[AC] Temperature Setpoint: Upper Limit
(Status)
[16 ... 30] ºC
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[EHS] Water Temperature: Upper Limit
(Status)
[5 ... 55] ºC
10
1 Byte
I
C - W - -
DPT_HVACContrMode
0=Auto
1=Heat
3=Cool
9=Fan
14=Dry
[AC] Mode
0 = Automatic; 1 = Heating; 3 =
Cooling; 9 = Fan; 14 = Dry
11
1 Byte
O
C R - T -
DPT_HVACContrMode
0=Auto
1=Heat
3=Cool
9=Fan
14=Dry
[AC] Mode (Status)
0 = Automatic; 1 = Heating; 3 =
Cooling; 9 = Fan; 14 = Dry
12
1 Bit
I
C - W - -
DPT_Heat_Cool
0/1
[AC] Simplified Mode
0 = Cooling; 1 = Heating
13
1 Bit
O
C R - T -
DPT_Heat_Cool
0/1
[AC] Simplified Mode (Status)
0 = Cooling; 1 = Heating