KLIC-SG allows controlling the A/C unit operating mode through the following objects,
available by default:
“[AC] Mode”
: 1-Byte object which allows selecting the A/C unit operation
mode. There will be only taken in account values that are appropriated with
some of available modes in Samsung units, which are represented in Table 1.
“[AC] Mode (status)”
: 1-Byte object which allows knowing the A/C unit
operating mode status.
Object Value
A/C unit mode
0
Auto
1
Heating
3
Cooling
9
Fan only
14
Dry
Table 1.
A/C unit operating modes.
Additionally, a simplified mode can be configured to select Cooling and Heating mode.
Simplified Mode (Only Cooling/Heating)
[
disabled
/enabled
]: in addition to
the “
Mode
” and “
Mode (Status)
” 1-Byte objects, available by default, it is
possible to commute and to verify the current operation mode through the
following 1-Bit objects, which get enabled after activating this parameter:
“
Simplified Mode
”, which allows switching to the Cooling mode by
sending
it a “0” and to the Heating mode by sending it a “1”.
“
Simplified Mode (Status)
”, which will send a value of “0” when the mode
switches to Cooling or to Dry, or a value of “1” when it switches to Heating.
The Fan and Auto modes are not reflected in the value of this object.
VENTILATION
Figure 7.
A/C Gateway. Configuration. Ventilation.