KLIC-SG
Technical Support:
8
A/C Gateway
[
enabled
]
1
: enables the “A/C Gateway” tab in the tree on the left.
For more information, see section 2.2.
Inputs
[
disabled
/enabled
]: enables or disables the “Inputs” tab in the tree on
the left, depending on whether the device will or will not be connected any
external accessories. For more information, see section 0.
Logic Functions
[
disabled
/enabled
]: enables or disables the “Logic Functions”
tab in the tree on the left. For more information, see section 2.3.
Heartbeat (Periodic Alive Notification)
: this parameter lets the integrator
incorporate a 1-B
it object to the project (“
[Heartbeat] Object to Send ‘1’
”) that
will be sent periodically with value “1” to notify that the device is still working
(
still alive
).
Note
:
the first sending after download or bus failure takes place with a delay
of up to 255 seconds, to prevent bus overload. The following ones match the
period set.
Figure 4.
Heartbeat.
Regardless of the above parameters, the following objects are available by default:
“
[AC] On/Off
” and “
[AC] On/Off (Status)
”: allow switching on (value “1”) and
off (value “0”) the A/C unit or reading the current status, respectively.
“
[AC] Temperature Setpoint
” and “
[AC] Temperature Setpoint (Status)
”:
allow setting the desired temperature setpoint or reading the current value,
respectively. See section 2.2.1 for further options.
1
The default values of each parameter will be highlighted in blue in this document, as follows:
[
default
/rest of options
].