KLIC-SG
Technical Support:
25
On/Off
[
Last (Before Restart)
/ On / Off
].
Mode
[
Last (Before Restart)
/ Automatic / Heating / Cooling / Fan / Dry
].
Fan speed
[
Last (Before Restart)
/ Auto / 1 / 2 / 3
]. The number of speeds
(
“
Auto
/ 1 / 2 / 3
” or “
Auto
/ 1 / 2 / 3 / 4
”) will depend on those selected in the
Fan speeds
parameter, in the
“Fan” tab. See section 2.2.2.
Air Flow Direction
3
[
Last (Before Restart)
/ Spot / Mid / Wide / Swing
].
Horizontal Flaps
[
Last (Before Restart)
/ Swing Off / Swing On
].
Vertical Flaps
[
Last (Before Restart)
/ Swing Off / Swing On
].
Setpoint
[
disabled
/enabled
]
:
Value:
[
Last (Before Restart)
]: the value of the setpoint temperature will be kept.
Only available if the
Setpoint
parameter remains disabled.
[
16…
25
…30
] ºC.
Note
:
this initial setpoint value may be modified by the setpoint limits during
runtime.
Send initial configuration
[
disabled
/enabled
]:
If enabled, the status objects
will be sent to the KNX bus after applying the parametrized
delay
[0
…
10
…3600], in seconds.
Notes
:
Even if this option is not enabled, the status objects may be sent to the
KNX bus if the initial configuration differs from the current status of the
A/C machine.
The delay parametrized in initial configuration sending is approximate,
due to it starts to be counted when the communication between KLIC-SG
and A/C unit is confirmed.
3
This option is only available if
360 CST
is selected in the “Fan” tab.