background image

BACnet Gateway

MIM-B17

Air Conditioner

installation manual

DB98-32390A(3)

E

imagine

 the possibilities

Thank you for purchasing this Samsung product. 

MIM-B17_BACnet Gateway_IM_E 32390-3.indd   65

2011-04-04   오후 3:44:31

Summary of Contents for MIM-B17

Page 1: ...BACnet Gateway MIM B17 Air Conditioner installation manual DB98 32390A 3 E imagine the possibilities ThankyouforpurchasingthisSamsungproduct ...

Page 2: ...N Do not use inflammable gases near the BACnet Gateway Do not install the BACnet Gateway in a location where it will come into contact with combustible gases machine oil sulphide gas etc Avoid locations where acid alkali solution or special spray is used Choose a location that is dry and sunny but not exposed to direct sunlight Suitable temperature is between 0 C 32 F and 39 C 102 2 F Do not spill...

Page 3: ...le Devices 10 Installing the BACnet Gateway 12 Setting the BACnet Gateway 17 Reading EHPWatt hour Meter 22 System Setting Initialization 27 System Settings 28 Tracking 37 Device Configuration 43 BACnet Protocol Implementation Conformance Statement 51 Standard Object Types Supported 55 Detail Description of Object 56 BACnet Point List 57 Other Information 61 ...

Page 4: ...n cables from centralized controllers interface modules must be installed in such a way that the wires can be connected to the BACnet Gateway with ease Note TheBACnetGatewayisaserverandsupportsstaticIP ToaccesstheBACnetGatewaythroughtheinternetor withBMSSystem theBACnetGatewayaddress which istheIPaddress mustbeknown AstaticIPservicefromaninternetserviceprovider mustbeusedifxDSL ADSL VDSL isbeingus...

Page 5: ...ems may vary depending on your country or service provider Accessories The BACnet Gateway must be installed by a trained installer Ensure the main power is turned off before installing the BACnet Gateway Be sure to use adapter and power cable we provide The power cable and the communication cable must be installed according to the national electrical wiring regulations ...

Page 6: ...or Turns blue when the power is supplied CPU Alive CPU operation indicator Blinks in orange with 1 second intervals during normal operation Ethernet Linked Internet connection indicator Turns green during normal connection Ethernet Active Internet data transmission reception indicator Blinks in orange during normal transmission reception COM1 5 TX Channel 1 5 Centralized controller Interface modul...

Page 7: ...inal Service agent checks BACnet Gateway error status using this terminal SD card socket Sub memory for program update and set information saving socket RS485 Communication Terminal Connect for RS485 communication with devices such as centralized controller Interface module COM1 COM5 Ethernet Terminal Connect LAN cable Cable tie groove Groove for arranging cables Cable tie groove SD Card Socket Se...

Page 8: ... mm Display Board 40 pin Cable 20 pin Cable Main Board Sub Board BACnet Gateway Interior Main Parts Viewing the Parts Continued Note If you need external circuit configuration consult with the manufacturer Product Dimensions ...

Page 9: ...erface module WhenconnectingcentralizedcontrollerandinterfacemoduletotheBACnetGateway ofsamecommunicationchannel onlyoneofthemwillcommunicateaccordingtothe communicationchannelmodesettingof SystemSettings Tracking Therefore donotconnectthecentralizedcontrollerandinterfacemoduletothesame communicationchannel Ifyousetthecommunicationchannelmodeasinterfacemodule virtualcentralized controlleraddresswi...

Page 10: ...c MIM B13A DVM PLUS II DVM PLUS III DVM PLUS IVetc MIM B13B MIM B13D MIM B13E 6 Watt hour Meter RS485 comm type Connected with SIM Needed for power distribution Please consult Samsung for compatible power meters Pulse type Connected with PIM Pulse Width 20 400 ms Pulse 1 10000 Wh Pulse Products with are not Samsung products and must be purchased separately Only selected power meters may be used fo...

Page 11: ...ts Interface module 80 16 units per 1 channel total 80 units are connectable when connecting interface module to BACnet Gate way directly 256 units are connectable when using centralized controller SIM PIM 8 Up to 8 units are connectable Watt hour Meter 64 8 units are connectable per 1 SIM PIM Maximum Devices Attachable ...

Page 12: ...ing the BACnet Gateway 1 Separate the installation plate on the rear side of BACnet Gateway 2 Fix the installation plate on the wall using 4 screws 3 Hang the BACnet Gateway on the groove which is on the top of the installation plate ...

Page 13: ... BACnet Gateway using assistant holes Screws for assistant hole are not provided by our company 5 If you install BACnet Gateway inside of the wall or wiring from the rear side is needed use wiring groove on the bottom of BACnet Gateway TopreventbreakdownanddamageofBACnetGateway and forsafeusage itisrecommendedtoinstallBACnetGatewayon thewall ...

Page 14: ... 2 Connect the adapter to the power terminal Arrange the adapter as the right figure 3 Separate 1 terminal block from 5 terminal blocks which are attached to RS485 communication terminal Then connect interface communication cable C1 C2 to the terminal block C1 A C2 B 4 Connect LAN cable to the Ethernet terminal of BACnet Gateway Then arrange it using cable tie 5 Fasten the bottom cover of BACnet G...

Page 15: ...o the power terminal Arrange the adapter as the right figure 3 Separate 1 terminal block from 5 terminal blocks which are attached to RS485 communication terminal Then connect interface module communication cable R1 R2 to the terminal block R1 A R2 B 4 Connect LAN cable to the Ethernet terminal of BACnet Gateway Then arrange it using cable tie 5 Fasten the bottom cover of BACnet Gateway and fix it...

Page 16: ...nal Arrange the adapter as the right figure 3 Separate 1 terminal block from 5 terminal blocks which are attached to RS485 communication terminal Then connect SIM PIM communication cable C1 C2 to the terminal block C1 A C2 B 4 Connect LAN cable to the Ethernet terminal of BACnet Gateway Then arrange it using cable tie 5 Fasten the bottom cover of BACnet Gateway and fix it using 2 screws Maximum8SI...

Page 17: ... twice on your computer 2 When internet explorer window appears enter IP address http 192 168 0 100 on the address bar then press ENTER 3 If it is the first time to access BACnet Gateway Install Microsoft Silverlight message will appear If Microsoft Silverlight have already installed the screen will not appear ...

Page 18: ...Continued 4 Click Run button and continue installation After installation access to BACnet Gateway again Silverlight operates normally with Windows XP SP2 or later version It may not operate normally with previous version of Windows 4 ...

Page 19: ... management To use the BACnet Gateway functions you must login with the ID that is included in administration group Factory default BACnet Gateway ID is admin and password is 1234 Note Onlyauthorizeduserscanaccesstowebpage Connectionspeedmayslowdown Fewerthan5concurrentusersare recommended BACnetGatewaymanagershouldchangeIDandpasswordforsecurityand management Logout Ifyouwanttologout click LOGOUT ...

Page 20: ...ick System Setting BACnet configuration menu to switch to BACnet Gateway If you use accounts with authorization level lower than management group or accounts with general authorization level BACnet configuration will not be displayed on the menu If the BACnet configuration menu does not appear consult the manager 6 ...

Page 21: ...E 21 7 If you access BACnet Gateway Device Configuration screen will appear initially If you click DMS2 Connect button screen will be switched to initial screen 7 ...

Page 22: ...r meter You can use maximum 16 letters for name and only available special characters are _ and space Value for CT proportion should be integer between range of 1 5000 4 Click Save CT proportion value will be saved to the BACnet Gateway If you do not click Save changed setting will not be saved 5 Watt hour meter value will display the actual value of electricity on the corresponding watt hour mete...

Page 23: ...ist box enables 3 Set the Monthly baseline setting You can select from 1 31 If you select the last day of the month it will automatically set the last day of corresponding month as baseline Ex Last day of February 28th or 29th 4 Click Save Changed settings will be saved to the BACnet Gateway If you do not click Save changed setting will not be saved 1 2 4 ...

Page 24: ... setting text box will be enabled and you can enter the period in daily unit If you select monthly period setting you can select the period in monthly unit 3 Set the period If you set period in daily unit you can set up to maximum 90 days If you set period in monthly unit you can set up to maximum 1 months 4 Click Save Changed setting will be saved to BACnet Gateway If you do not click Save change...

Page 25: ...een 3 Check the address and the channel information of the SIM PIM interface module which is connected to the watt hour meter If the SIM interface modules with addresses 0 7 executes tracking it will be displayed as 16 23 in BACnet Gateway 4 Check the information of indoor outdoor unit which is connected to watt hour meter 3 7 2 1 ...

Page 26: ...ndoor unit to execute power distribution If you do not set the watt hour meter information the power distribution result of the indoor unit will be displayed as 0 7 Click Save Changed setting will be saved to BACnet Gateway If you do not click Save changed setting will not be saved Information of watt hour meter connected to indoor outdoor unit should be accurate If the watt hour meter information...

Page 27: ...s Menu Menu buttons in order from the main menu screen Caution will be displayed on LCD Display 3 Initialize BACnet Gateway by clicking Set when caution phrase appears If you press Menu button system will return to main menu without initialization When initializing system setting all saved data in BACnet Gateway will be deleted After initialization you must aware that the saved data and IP address...

Page 28: ...om the BACnet network information section 3 When text boxes of IP Subnet mask Default gateway Device Instance No and DNS server are enabled Enter values for each item 15 letters can be entered for each item Each item should match with the network address form You can enter from 1 to 16 for Device Instance No 4 Click Save button on the BACnet network information section 1 2 4 3 ...

Page 29: ...engineerIP 192 168 0 254 isappliedtoeachBACnet Inthiscase edittheserviceengineerIPbyfollowingbelowinstructionsandthen usetheIP 1 RunDOScommandwindowbyentering cmd fromWindows Start Run 2 AccesstoBACnetGatewaybyrunning telnet192 168 0 254 fromDOS commandwindow 3 EnterID PASSWORD 4 Edit sysenv file IPsettingrelatedfile asbelow Run sudovi mnt nand0 config sysenv fromtelnetconnectionscreen Find IP2 19...

Page 30: ...enter from 1 to 12 Day You can enter from 1 to 31 Hour You can enter from 0 to 23 Minute You can enter from 0 to 59 Second You can enter from 0 to 59 4 Click Save button on the System time section 5 When the pop up window appears click OK When message with Reading data from DMS Please wait appears saving is completed Then System Settings screen appears again with all items disabled Note Systemtime...

Page 31: ...ck System Settings 2 Click Edit from the Select language section 3 Select a language you want and click Save 4 When the pop up window appears click OK BACnet Gateway will restart and the system will be changed to selected language 1 2 ...

Page 32: ...2 Level Emergency stop Commands to stop all operation of indoor unit except DDC and disable remote control when inputting contact control signal In level emergency stop status it will not be controllable even if the command is from upper controller Pattern 3 Level Operation Stop Level signal input timing It changes operation stop status of all indoor units Pattern 4 Pulse Operation Stop Disable En...

Page 33: ...ings screen appears again with all items disabled Note Contactpointcontrolpatternissettopattern1asfactorydefault For extension purpose BACnet Gateway has total of 10 DI DO ports Contact control and output function is assigned to Ch1 and Ch2 Ch3 Ch10 will be assigned to additional functions For proper contact control connect with Ch1 and Ch2 5 ...

Page 34: ...iven Operation command 2 If the contact signal of port 1 changes from ON to OFF all indoor units will be given Stop command 3 If the contact signal of port 2 is OFF you cannot control all indoor units using remote controller 4 If the contact signal of port 2 changes from OFF to ON you can control all indoor units using remote controller 5 If the contact signal of port 2 changes from ON to OFF you ...

Page 35: ... BACnet Gateway CH1 CH2 BACnet Gateway Pattern 3 External contact signal control Pattern 4 Pulse signal control Emergency Stop Resume Operation No Connection Operation Stop A C Enable Disable remote control Operation Stop A C A C DI Digital Input Circuitry according to Control Switch Pattern ...

Page 36: ...E 36 BACnet gateway information 1 Click System Settings 2 You can check the basic BACnet gateway information from BACnet gateway information section System Settings Continued 1 ...

Page 37: ...e for each device You can set name for connected device Set the names to help you recognize the location of the device easily Communication mode setting for each channel Roles It records what devices are connected to COM1 COM5 of BACnet Gateway Through tracking BACnet Gateway searches proper devices that fits to user s setting Select proper communication mode which fits to connected device What is...

Page 38: ...h channel 1 Click Device Configuration 2 Click Edit from the Communication mode by channel screen Edit button will be switched to Cancel All selection buttons will be enabled However the channels with searched device maintain its button in disabled status 1 2 ...

Page 39: ...ce module and SIM interface module is possible If you set interface module as communication mode tracking monitoring controlling centralized controller and SIM interface module is possible 4 Click Save after setting is completed If you click Cancel check boxes will be disabled and Cancel button will switch to Edit 5 When message with Reading data from DMS Please wait appears saving is completed Th...

Page 40: ...E 40 Tracking Continued DVMTracking 1 Click Device Configuration 2 Click DVM Tracking 1 2 ...

Page 41: ...mode set to Interface module tracking will be executed on the interface modules within range of D0 DF and SIM interface modules Channels with communication mode set to Centralized controller tracking will be executed on centralized controller and SIM interface module 6 Pop up window with message Tracking is in progress Please wait will appear Tracking takes from few seconds to 3 minutes However it...

Page 42: ...esetto11 Channel1to12 Channel2to13 channel3to14andchannel4to15 Ifthereisexistingcommunicationchannelforinterfacemodule trackingforcentralized controllerwillbelimitedtorangeof0 10 Ifyoucannotfindanydevicesaftertracking itwillbeconsideredasaDVMtracking failure Iftherearedeviceswhichhavesameaddress onlyfirstsearcheddevicewillbe registered Thenumberofcentralizedcontrollercontainsthenumberofvirtualcent...

Page 43: ...us in BACnet Gateway Monitoring and controlling of all the connected devices to BACnet Gateway will be stopped when you use this function Connect searched device to the other channel and execute tracking If the other device is searched in the channel you want to use use Disconnect all devices function If you use this function BACnet Gateway device connection status will be initialized 3 4 1 2 ...

Page 44: ...lick OK to continue 6 When message with Reading data from DMS Please wait appears and all the devices are disconnected page will be refreshed Note Afterexecuting Disconnectalldevicefunction devicesearchstatusofBACnet Gatewaywillbeinitialized Youshouldexecutetrackingagainafterusingdisconnectalldevicesfunction 5 ...

Page 45: ...arched by tracking click Edit in the bottom of the list Edit will be changed to Cancel Note Ifyouclick Cancel button Cancel buttonwillbeswitchedto Edit buttonandthe changednameofdeviceswillberestoredtooriginalname Renaming the devices 1 ...

Page 46: ...l characters within the device name 3 Click Save after setting is completed If you click Cancel text boxes will be disabled and the Cancel button will be switched to Edit 4 When message with Reading data from DMS Please wait appears saving is completed Then Tracking screen appears again as all items are disabled 2 3 ...

Page 47: ...E 47 1 Click one of the Object ID from Object ID column Detail information of the selected device will be displayed in device information Checking device information 1 ...

Page 48: ...e current value of the corresponding object Unit will be displayed between 3 You can enter numbers to modify the Output type objects Click Edit button on the bottom of the Device configuration screen and enter the value when the text box enables 4 Click Save after setting is completed If you click Cancel text boxes will be disabled and the Cancel button will be switched to Edit 5 When message with...

Page 49: ...esponding object It will be displayed either On or Off 7 You can select the values to modify the Output type objects Click Edit button on the bottom of the Device configuration screen and select the value from On or Off when the button enables 8 Click Save after setting is completed If you click Cancel buttons will be disabled and the Cancel button will be switched to Edit 9 When message with Read...

Page 50: ...e values to modify the Output type objects Click Edit button on the bottom of the Device configuration screen and select the value when the list box enables 12 Click Save after setting is completed If you click Cancel buttons will be disabled and the Cancel button will be switched to Edit 13 When message with Reading data from DMS Please wait appears saving is completed Then Device configuration s...

Page 51: ...tion Specific Controller B ASC BACnet Smart Sensor B SS BACnet Smart Actuator B SA List all BACnet Interoperability Building Blocks Supported Annex K SUPPORTED BIBBS BIBB NAME SUPPORTED REMARKS Data Sharing DS RP A Data Sharing ReadProperty A DS RP B Data Sharing ReadProperty B DS RPM A Data Sharing ReadPropertyMultiple A DS RPM B Data Sharing ReadPropertyMultiple B DS RPC A Data Sharing ReadPrope...

Page 52: ...T I B Viewing and Modifying Trends Internal B T VMT E B Viewing and Modifying Trends External B T ATR A Automated Trend Retrieval A T ATR B Automated Trend Retrieval B T VMMV A Viewing and Modifying Multiple Values A T VMMV I B View and Modifying Multiple Values Internal B T VMMV E B View and Modifying Multiple Values External B T AMVR A Automated Multiple Value Retrieval A T AMVR B Automated Mult...

Page 53: ... Configuration B Object Type Supported Dynamically Creatable Dynamically Deletable Writeable Properties Analog Input Present value Analog Output Present value Analog Value Present value Binary Input Present value Binary Output Present value Binary Value Present value Calendar Command Device Yes n a n a n a Event Enrollment File Group Loop Multi state Input Present value Multi state Output Present ...

Page 54: ...vices Yes No Networking Options Router Clause 6 List all routing configurations e g ARCNET Ethernet Ethernet MS TP etc Annex H BACnet Tunneling Router over IP BACnet IP Broadcast Management Device BBMD Does the BBMD support registrations by Foreign Devices Yes No Does the BBMD support network address translation Yes No Character Sets Supported Indicating support for multiple character sets does no...

Page 55: ...ture limit Averaging Binary Input DI Filter sign status Binary Output DO Filter sign reset Binary Value Power On Off control Setting the fucntion of limiting lower temperature Setting the function of limiting upper temperatue Calendar Command Device DMS A C Indoor Unit ERV AHU SIM Centralized controller Interface module DDC Event Enrollment File Group Life Safety Point Life Safety Zone Loop Multi ...

Page 56: ...dual address 400 1x16 1 417 Ex Indoor Unit DNET Gateway number 9 Indoor Unit Address 01 01 32 Device ID 941732 9 417 32 Item DNET Range Digit 2 CPP Range Digit 3 INDOOR Range Digit 2 Centralized Controller 0 15 000 015 64 SIM 0 15 100 115 64 DMS DI DO 0 15 300 315 64 Interface Module 0 15 400 655 16 x 16 64 Indoor Unit ERV AHU kit 0 15 400 655 0 63 Gateway 0 15 900 64 Object of device Detail Descr...

Page 57: ...mperature limit setting BV AC_Cool_Limit_set_xx_ xxxxxx Off On 11 Applying upper temperature limit setting BV AC_Heat_Limit_set_xx_ xxxxxx Off On 12 Filtersignstatus BI AC_FilterSign_xx_ xxxxxx Off On 13 Filtersignreset BO AC_FilterSign_Reset_ xx_xxxxxx Off On 14 Operationmodestatus MV AC_Operation_Mode_ xx_xxxxxx Auto Cool Heat Fan Dry 15 Fanspeedstatus MV AC_FanSpeed_xx_ xxxxxx Auto Low Mid High...

Page 58: ..._Period_kWh_xx_ xxxxxx kWh 8 The number of hours usage of an indoor unit within period AI AHU_Period_Minute_ xx_xxxxxx Minute 9 Power On Off BV AHU_Power_xx_ xxxxxx Off On 10 Applying lower temperature limit setting BV AHU_Cool_Limit_set_ xx_xxxxxx Off On 11 Applying upper temperature limit setting BV AHU_Heat_Limit_set_ xx_xxxxxx Off On 12 Filter sign status BI AHU_FilterSign_xx_ xxxxxx Off On 13...

Page 59: ...er_xx_xxxxxx Off ON 2 Filter sign status BI ERV_FilterSign_xx_ xxxxxx Off ON 3 Filter sign reset BO ERV_FilterSign_Reset_ xx_xxxxxx Off ON 4 Operation mode status MV ERV_Operation_ Mode_xx_xxxxxx Auto HeatEx Bypass Sleep 5 Fan speed status MV ERV_FanSpeed_xx_ xxxxxx Low High Turbo 6 Remote controller limit status MV ERV_Remocon_Limit_ xx_xxxxxx Work Fully Limited Power On Limited 7 Integrated erro...

Page 60: ...ralized controller error code AI Central_Error_ Code Refer to the list of the integrated error code Centralized controller Instance Number Object Object Type Object Name Status value 1 Interface module error code AI Repeater_Error_ Code Refer to the list of the integrated error code Single Interface module has following point list Interface module Instance Control and Monitoring Object Type Object...

Page 61: ...1 Reliability property will be set as COMMUNICATION_FAILURE 2 Fault Alarm flag of Status_Flags property will be set as TRUE 3 Present_Value property is readable but the value is not guaranteed Main service Time setting Time synchronization Service is a service that allows the time of BACnet Gateway to be synchronized with the time of PC COV Change Of Value COV service is supported and you can set ...

Page 62: ...E 62 Memo ...

Page 63: ...E 63 ...