E-
56
Device
Following table shows regulation of device ID and they are created automatically.
Refer to BACnet point List
DNET (Gateway number)
Centralized
Controller address
Interface Module
address
Indoor Unit Individual address
400 + 1x16 + 1 = 417
Ex) Indoor Unit
DNET (Gateway number): 9
Indoor Unit Address: 01.01.32
Device ID: 941732
9
417
32
Item
DNET – Range
[Digit 2]
CPP – Range
[Digit 3]
INDOOR – Range
[Digit 2]
Centralized
Controller
0~15
000~015
64
SIM
0~15
100~115
64
DMS DI/DO
0~15
300~315
64
Interface Module
0~15
400~655
(16 x 16)
64
Indoor Unit
ERV
AHU kit
0~15
400~655
0~63
Gateway
0~15
900
64
Object of device
Detail Description of Object