22 EN
Meaning of the
error messages
Code Description
A0
NTC sensor Tge is faulty.
(= Temperature of the outside
air for base exchanger)
A1
NTC sensor T1 is faulty.
(= Temperature of the intake
air)
A2
NTC sensor T2 is faulty.
(= Temperature of the supply
air)
A3
NTC sensor T3 is faulty.
(= Temperature of the extract
air)
A4
NTC sensor T4 is faulty.
(= Temperature of the exhaust
air)
A5
Malfunction in the bypass
motor.
A6
Malfunction in the motor of the
frost-free element
A7
Frost-free element not heating
sufficiently.
A8
Frost-free element becomes
too hot.
A10
NTC sensor Tch is faulty.
(= Temperature in the Comfo-
Hood)
A11
NTC sensor Tah is faulty.
(= Temperature of the reheater)
E1
Extract fan not rotating.
E2
Supply fan not rotating.
E3
Temperature sensor Comfo-
Hood too high.
E4
The ventilation unit has been
switched off by external contact
EA1
Enthalpy sensor measures
excessively high Relative
Humidity (RH) values.
EA2
The ventilation unit is not com-
municating with the enthalpy
sensor.
EA15 CC Luxe is not communicating
with the ventilation unit.
Code Description
EA16 CC Luxe is not communicating
with the ComfoCool.
Filter
Filter is dirty
C1
Condenser of the ComfoCool
becomes too hot.
C2
Malfunction in the compressor
of the ComfoCool.
C3
NTC sensor Tcon of the
ComfoCool is faulty
(= Temperature of the
condenser).
C4
NTC sensor Tin of the
ComfoCool is faulty
(= Temperature of the supply
air)