EN 11
Time delay values
Submenu
description
Minimum Maximum Factory reset
P22
(Optional)
Note:
only applies to
systems fitted with
a corded switch in
the bathroom.
Deactivation delay for the bathroom
switch (to switch to normal setting).
• ‘x’ minutes after operating the bath-
room switch, the ventilation unit
switches to the
n orm al
s e ttin g
.
- Low voltage input
0 Min.
120 Min.
30 Min.
P23
(Optional)
Note:
only applies to
systems fitted with
an hardwired
3-position switch.
Deactivation delay for ventilation set-
ting 3.
• If you BrIEFLY engage ventilation
setting 3 (<3sec.), the ventilation unit
switches to the HIGH SETTING for
“x” minutes and then switches back
automatically to the normal ventila-
tion setting.
If a 3-position switch is operated during
the time delay mode, then the ventila-
tion unit switches immediately to the
selected ventilation setting.
0 Min.
120 Min.
0 Min.
P24
Filter warning
• Here the user can indicate when the
“
filter
dirty
” alert must appear.
10 weeks 26 weeks
16 weeks
P25
Note:
only applies to
systems fitted with
an rF switch.
Deactivation delay for ventilation setting
3 (using “
”).
• After pressing “
” BrIEFLY (<2
sec.), the ventilation unit switches to
the HIGH SETTING for ‘x’ minutes
and then switches back automati-
cally to the normal ventilation set-
ting.
If a 3-position switch is operated during
the time delay mode, then the ventila-
tion unit switches immediately to the
selected ventilation setting.
1 Min.
20 Min.
10 Min.