Charging Pile Instructions-V2.0
13
80kW
400V±15% AC
146A
90kW
400V±15% AC
165A
YJV22-0.6/1kV-3*70mm²
+2*35mm²
100kW
400V±15% AC
183A
120kW
400V±15% AC
219A
YJV22-0.6/1kV-3*95mm
²
+2*50mm
²
140kW
400V±15% AC
256A
YJV22-0.6/1kV-3*120mm
²
+2*70mm
²
150kW
400V±15% AC
274A
160kW
400V±15% AC
292A
YJV22-0.6/1kV-3*150mm
²
+2*70mm
²
Note: To ensure the power consumption safety of different onsite, the recommended cable
specification is relatively larger. Customer could choose proper cable according to actual
onsite situation.
(8) For current leakage breaker, specified type is recommended. See Chart 7.2.2 for details:
Chart 7.2.2 Current Leakage Specification
Output
power
Charging pile
User front-end distribution cabinet
Max.
Input
Current
Breaker
current
leakage setting
Breaker
Recommended
Breaker current
leakage setting
30kW
55A
300mA
(0.03~10A
Adjustable)
≥
100
>
300mA
40kW
73A
45kW
83A
60kW
110A
≥
160A
>
300mA
75kW
138A
80kW
146A
90kW
165A
≥250A
>
300mA
100kW
183A
120kW
219A
140kW
256A