FORM 155.32-ICOM2.EN.UL
SECTION 6 – OPERATION
ISSUE DATE:1/10/2018
JOHNSON CONTROLS
115
The
Gas
/
Oil
buttons select the fuel to use.
Purge Mode:
the
Auto
and
Manual
buttons control the purge operation. The lit button
indicates if the purge mode is Automatic or Manual.
Manual Purge:
The
ON
and
OFF
buttons control the manual purge operation. The lit
button tells you if the manual purge operation is running or not. If you press the Purge
Mode
Auto
button, the purge is done automatically. If you press the Purge Mode
Manual
button, the purge starts when you press the Manual Purge
ON
button. The purge stops
when you press the Manual Purge
OFF
button.
Purge Route (if available):
Indicates whether the purge route to be used is from the purge
tank or the absorber. The
Tank
and
Abso
buttons select the purge route to be use.
SELECT LANGUAGE
Press the button to choose the language to be shown in the Control Center. Various
languages are available: in this instance, Japanese, English, and Chinese.
BURNER CONTROL PANEL
For interface information on the burner control, refer to the
Power Flame
-
Model C Burner
Installation and Operation Manual, Section 3 - Control Panel Information
.
Figure 56 -
Burner Control Panel
In this section, choices can be made about the mode of operation for the various devices.
Use the buttons to make your choice. The choices are:
Light Indicators:
Call for Operation:
when light is lit, the burner must be started, otherwise the light will be off.
Ignition On Light:
when the burner should be igniting, the light will be on. After ignition, the
light turns off.
Main Fuel
: when the main fuel valve is open, the light is on; when the main fuel valve is
closed, the light is off.
Flame Failure
: When the flame is off, the light is on.
Control Switch
: ON/OFF switch determines if you’d like the burner to run or stop. Select
the burner
run
or
stop.
Fuel Changover:
Allows for the selection of different fuel.
AZL Display:
Hand communicator for the burner management system.
Alarm Buzzer:
When the alarm is activated, the buzzer becomes active.
AZL Display:
Hand communicator for the burner management system.