Rupture Disk Discharge Piping Sizing
The sizing of the rupture disk discharge piping must not be less than the rupture disk
diameter. Where two or more relief devices are connected to a common line or header the
effect of back-pressure that will be developed when more than one relief device operates
shall be considered. The sizing of the discharge line for above condition must be based on
the sum of each rupture disk outlet area in addition to the pressure drop allowance through
the outlet piping.
Figure 9 -
Location of Rupture Disk
Figure 10 -
Location of Rupture Disks
LD27779
Absorber
Condenser Rupture disk
Low-temperature generator
Burner
Evaporator
LD27800
Rupture disk
Control panel
Pressure switch
Burner flange
Optional hot water
heat exchanger
Pressure gauge
HTG. pressure detector
Purge tank
Pressure release valve
Low-temperature
generator
High-temperature generator