-P- Alarm settings
-r- Temperature control
Upon entering this submenu the dynamic
set point
tempera-
tures (if this function is enabled) are displayed. Press
Up
to
access the configuration menu.
DESCRIPTION
RANGE
UNIT
VALUE
High pressure alarm set point (transducer B3; B4)
0/99.9
bar
41
High pressure alarm differential (transducer B3; B4)
0/99.9
bar
10
Low pressure alarm, summer
0/99.9
bar
3
Low pressure alarm, winter
0/99.9
bar
2
Low pressure alarm, defrost
0/99.9
bar
1
Low pressure differential
0/99.9
bar
1
Start low pressure alarm delay
0-999
s
60
Operating low pressure alarm delay
0-999
s
0
Start flow switch alarm delay
0-999
s
20
Operating flow switch alarm delay
0-999
s
5
Number OFF cycles per auto reset alarm
0 - 4
1
Max. period for auto. reset alarm
0 - 99
m
60
Selection alarm with auto reset: compressor thermal switch
AUTOMATIC / MANUAL
AUTOMATIC
Selection alarm with auto reset: fan thermal switch
AUTOMATIC / MANUAL
AUTOMATIC
Selection alarm with auto reset: low pressure switch
AUTOMATIC / MANUAL
AUTOMATIC
Selection alarm with auto reset: high pressure switch
AUTOMATIC/ MANUAL
AUTOMATIC
DESCRIPTION
RANGE
UNIT
VALUE
COOL set point
°C
12
HEAT set point
°C
40
Temperature setting band
°K
3
COOL set point lower limit
°C
6
COOL set point upper limit
°C
15
HEAT set point lower limit
°C
25
HEAT set point upper limit
°C
45
Enable dynamic set point
N/Y
-
N
Max. compensation value
-99.9/99.9
°K
5
Compensation in COOL: start temperature
-99.9/99.9
°C
25
Compensation in COOL: end temperature
-99.9/99.9
°C
35
Compensation in HEAT: start temperature
-99.9/99.9
°C
7
Compensation in HEAT: end temperature
-99.9/99.9
°C
12
Type of temperature setting
INPUT/OUTPUT
-
INPUT
Type of setting with input probe
PROPORTIONAL/P+I
PROPORTIONAL
Type of integration in each adjustment P+1
0/9999
s
600
Max. time call increase (output setting)
0/9999
s
20
Min. time call increase (output setting)
0/9999
s
20
Max. time call decrease (output setting)
0/9999
s
10
Min. time call decrease (output setting)
0/9999
s
10
Temp. differential within flow varies increase & decrease time (output setting)
-99.9/99.9
°C
2
Device forced OFF in COOL cycle (output setting)
-99.9/99.9
°C
5
Device forced OFF in HEAT cycle (output setting)
-99.9/99.9
°C
47
Enable dynamic set point
Y/N
N
Min. dynamic set point
-99.9/99.9
°C
0
Máximo
set point
dinámico
-99.9/99.9
°C
5
Summary of Contents for YCSA 120 T
Page 2: ......
Page 4: ......
Page 23: ...23 Minimum technical clearance ...
Page 24: ...24 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Page 26: ...26 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Page 27: ...27 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Page 29: ...29 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Page 30: ...30 Wiring YCSA YCSA H 120 and 150 T TP ...
Page 35: ...35 General wiring diagram ...
Page 48: ...www johnsoncontrols com ...