43
2. Setting by means of the water temperature at the ex-
changer
outlet
.
Thermostatic control is based on the temperature value
detected by probe B6.
The set point value (STPM) and the regulating band (RBM)
define a neutral temperature zone (NZ).
- The temperature values comprised between the set point
and the set point plus the band (STPM
≤
Temperature
≤
STPM + RBM) do not cause compressor ON/OFF cy-
cles.
- Temperature values above the set point plus the band (Tem-
perature > STPM + RBM) cause compressor operation.
- Temperature values below the set point (Temperature
< STPM) turn the compressors off.
The compressor ON/OFF process is governed by a variable
delay period.
As of the time differential calculated as a delay, and in accord-
ance with the average temperature for probe B6, the control
system modulates ON/OFF cycles of the compressors.
If value 0 is set, the minimum delay increase/decrease time
of a call for power disables this function.
There is a differential temperature, which is different for opera-
tion in heat or cool cycle (below or above...), that turns off all
devices installed to avoid excessive heating/cooling.
STPM
Set point
RBM
Control band
NZ
Neutral zone
EOWT
Water temperature at exchanger outlet
DonZ
Compressor ON zone
DoffZ
Compressor OFF zone
TVD
Differential of phase input/output time variations
HTON
Stage activation maximum time delay
LTON
Stage activation minimum time delay
HT OFF Stage deactivation maximum time delay
LT OFF Stage deactivation minimum time delay
t
Time
�����
����
���
�����
��
�
���������
���
���
�����
����
����
����
�����
Summary of Contents for YCSA 120 T
Page 2: ......
Page 4: ......
Page 23: ...23 Minimum technical clearance ...
Page 24: ...24 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Page 26: ...26 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Page 27: ...27 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Page 29: ...29 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Page 30: ...30 Wiring YCSA YCSA H 120 and 150 T TP ...
Page 35: ...35 General wiring diagram ...
Page 48: ...www johnsoncontrols com ...