15
Table 4. Cooling capacities YCSA-H 120 - 150 T and TP
Integrated heating capacity, including defrost cycles
Table 5. Heating capacities YCSA-H 120 - 150 T and TP
Model
Water
outlet
temp.
°C
Outdoor ambient temperature °C DB (80% HR)
25
30
32
35
40
43
45
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
YCSA-H
120
T and
TP
5
123.5
36.7
114.7
39.9
111.3
41.2
106.0
42.0
97.4
46.4
92.0
48.3
88.5
51.2
6
126.5
37.3
118.0
40.3
114.6
41.6
109.4
42.4
100.9
47.2
95.6
48.9
92.2
51.6
7
129.7
37.9
121.3
40.7
117.9
42.2
114.0
43.3
104.4
48.0
99.3
49.6
96.0
52.0
8
132.8
38.5
124.6
41.1
121.2
42.9
116.3
44.2
108.0
48.8
103.1
50.2
99.8
52.4
10
139.1
39.6
131.1
42.0
127.9
44.2
123.1
45.0
115.1
49.5
110.4
50.9
107.2
53.3
12
145.6
40.4
137.3
43.6
134.1
45.0
129.3
47.0
121.3
50.3
116.4
52.3
15
154.8
43.3
146.6
46.2
143.3
47.4
138.5
49.1
130.4
51.9
YCSA-H
150
T and
TP
5
157.0
43.4
145.8
47.3
141.5
48.8
134.8
49.7
123.8
54.9
117.0
57.2
112.5
60.6
6
160.9
44.1
150.0
47.7
145.7
49.3
139.2
50.2
128.3
55.9
121.6
57.9
117.3
61.1
7
165.0
44.8
154.2
48.2
149.9
50.0
145
51.3
132.8
56.8
126.3
58.7
122.0
61.6
8
168.9
45.6
158.4
48.6
154.1
50.7
147.9
52.3
137.3
57.7
131.0
59.5
126.8
62.1
10
176.9
46.8
166.7
49.7
162.6
52.3
156.6
53.3
146.4
58.6
140.3
60.3
136.3
63.1
12
185.1
47.8
174.5
51.7
170.5
53.3
164.4
55.6
154.2
59.6
148.0
61.9
15
196.9
51.3
186.4
54.7
182.2
56.1
176.1
58.1
165.8
61.5
Model
Water
outlet
temp.
°C
Outdoor ambient temperature °C DB (80% HR)
-10
-5
-3
0
5
7
10
15
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
Cap.
kW
Unit
kW
YCSA-H
120
T and
TP
30
65.9
26.0
74.6
26.1
78.7
26.3
82.9
26.5
92.1
26.9
130.4
28.6
150.7
28.9
155.5
29.3
35
64.1
28.0
72.7
28.1
76.7
28.3
80.7
28.5
89.7
28.9
126.4
31.7
145.4
31.9
154.9
32.1
40
62.1
30.8
70.7
30.9
74.6
31.1
78.6
31.3
87.3
31.7
123.7
35.3
141.2
35.7
149.5
35.7
45
68.8
34.8
72.6
35.0
76.4
35.2
84.9
35.6
119.6
39.6
135.9
39.6
144.1
39.6
50
74.3
39.7
82.5
40.1
115.5
44.2
131.8
44.2
138.7
44.2
YCSA-H
150
T and
TP
30
82.0
35.2
93.6
35.3
98.8
35.6
104.0
35.8
115.5
36.4
163.5
38.7
189.0
39.1
195.0
39.6
35
79.7
37.9
91.1
38.0
96.2
38.3
101.3
38.5
112.5
39.1
158.6
42.9
182.4
43.1
194.3
43.3
40
77.3
41.6
88.7
41.7
93.6
42.0
98.6
42.3
106.5
48.2
155.1
47.7
177.2
48.2
187.5
48.2
45
86.3
47.1
91.1
47.3
95.9
47.6
106.5
48.2
150.0
53.5
170.4
53.5
180.8
53.5
50
93.2
53.6
103.5
54.1
144.9
59.7
165.3
59.7
174.0
59.7
Summary of Contents for YCSA 120 T
Page 2: ......
Page 4: ......
Page 23: ...23 Minimum technical clearance ...
Page 24: ...24 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Page 26: ...26 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Page 27: ...27 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Page 29: ...29 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Page 30: ...30 Wiring YCSA YCSA H 120 and 150 T TP ...
Page 35: ...35 General wiring diagram ...
Page 48: ...www johnsoncontrols com ...