42
F-r. Software version / language selection
- The version and revised date of the
µ
C3 software is dis-
played.
- The language to be used can be selected with keys
Up,
Down
and
Enter
: English or Italian.
Temperature setting
Two different modes are available (
Control Menu
):
1. Setting by means of the water temperature at the ex-
changer
intake
(probe B5).
This mode carries out a proportional type setting based on a
set point and a proportional band divided into 4 stages. This
type of control is included in the controller by default.
It is also possible to carry out a proportional and integral
setting. In this case, this function must be enabled and an
integration set point established (
Control Menu
).
Control sensor: B5 (entering water temperature of the ex-
changer).
Parameters to be used:
- Set point.
- Proportional band for intake setting.
- Type of setting (proportional or propor integral).
- Integration time set point (if the propor integral set-
ting has been enabled).
Control outputs: N1, N6 and N7 (compressor contactors).
Description of operation:
Temperature setting depends upon the average value de-
tected by the probe located at the exchange water intake. It
follows a proportional logic in which the proportional band is
subdivided into four equal stages that give way to compressor
ON/OFF cycles. In propor integral mode, operation is
similar, but affected by an algorithm that takes the time period
into account (
integration time set point parameter
).
STPM
Set point
RBM
Control band
EIWT
Temperature at interchanger intake
C1, 2, 3, 4
Stages/compressors
��
��
���
��
��
��
���������
�����������
���
��
��
���
��
��
��
���������
�����������
���
Summary of Contents for YCSA 120 T
Page 2: ......
Page 4: ......
Page 23: ...23 Minimum technical clearance ...
Page 24: ...24 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Page 26: ...26 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Page 27: ...27 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Page 29: ...29 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Page 30: ...30 Wiring YCSA YCSA H 120 and 150 T TP ...
Page 35: ...35 General wiring diagram ...
Page 48: ...www johnsoncontrols com ...