10
Units without pack
(1) Weight for unit empty. (2) Available static pressure, Eurovent certified. (3) Pressure with clean filter. (4) Weight with dual pump.
Sound power spectrum
Standard units
Units with hydro kit (version P)
Low noise level units
The data appearing in the tables are sound power values in compliance with the ISO EN 3743 standard.
No. of pumps
1
Available static pressure at rated flow
(without filter) for cooling mode (2)
kPa
231
205
Available static pressure at rated flow
(with filter) for cooling mode (3)
kPa
228
200
Pump consumption
W
3 180
3 400
Pump amperage
A
5.5
6.1
Unit water content
l
18 (T) / 170 (TP)
22.5 (T) / 179 (TP)
Expansion vessel volume
l
25
35
Relief valve setting
Bar
6
Max. unit power consumption
kW
58.3
74.5
Max. unit current amperage
A
108
120
Start-up amperage (compressor)
A
118
198
Weight (1) / (4)
kg
1 280 / 1 316
1 675 / 1 703
Start-up amperage (compressor)
A
118
198
Pressure drop
kPa
29.5
25.5
Max. unit power consumption
kW
53
71.1
Max. current amperage
A
103
114
Weight (1)
kg
1 220
1 615
Models
Hz
125
250
500
1 000
2 000
4 000
8 000
dB(A)
YCSA/YCSA-H 120
78
80
81
79
75
68
63
86
YCSA/YCSA-H 150
79
83
84
80
77
69
64
88
Models
Hz
125
250
500
1 000
2 000
4 000
8 000
dB(A)
YCSA/YCSA-H 120
75
76
77
73
59
58
53
82
YCSA/YCSA-H 150
76
78
79
73
68
59
54
84
Summary of Contents for YCSA 120 T
Page 2: ......
Page 4: ......
Page 23: ...23 Minimum technical clearance ...
Page 24: ...24 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Page 26: ...26 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Page 27: ...27 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Page 29: ...29 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Page 30: ...30 Wiring YCSA YCSA H 120 and 150 T TP ...
Page 35: ...35 General wiring diagram ...
Page 48: ...www johnsoncontrols com ...