47
Remote control unit
Wall-mounted, with push-buttons for COOL/HEAT and ON/OFF functions. Includes power supply, alarm and COOL/HEAT
LEDs. Prior to installation, these inputs must be validated on the H-unit config. menu, giving them value “Y”.
- The remote control unit can be located at a maximum distance of 50 m.
- Minimum cable section should be 0.35 mm².
- Avoid routing control cables near power cables.
Connection to control panel
1- Power supply LED
2- Alarm LED
3- ON/OFF selection push-button
4- Unit in operation LED
5- COOL/HEAT selection push-button
6- ON LED in heat operation/
OFF LED in cool operation
Data and measurements are subject to change without prior notice.
GO
D3
C10
N10
F3
24 Vac
REMOTE CONTROL
UNIT
CONTROL
PANEL
1
2
3
4
D15
GN
5
6
7
Alarm
ON/OFF
COOL/HEAT (1)
COMMON
(1) On heat pump units only.
�
�
�
�
�
�
�
��������������