JOHNSON CONTROLS
92
FORM 150.62-NM8 (1020)
UNIT CONTROLS
The third message indicates the system, and whether the
liquid line solenoid or EEV pilot solenoid and hot gas
solenoid are being turned ON by the I/O Board. Please
note that hot gas in not available for system 2, so there
is no message pertaining to the hot gas solenoid when
system 2 message is displayed.
The fourth message indicates what stage of condenser
fan operation is active. For YCAL0014 to YCAL0080
unless a low ambient kit is added, only stages 1 and 3
will be used to cycle the condenser fans. However, stage
2 may be shown in this display without a low ambient
kit added, but it has no effect. YCAL0090
through
YCAL0134 have 3 or 4 fan stages as standard.
See Condenser Fan Control in Section 2 of this IOM for
more information
.
The fifth message displays current as sensed by the
optional current feedback circuitry. The display reads
out in amps along with the DC feedback voltage from
the module. Current is calculated by:
`
Individual displays will be present for each system,
if CURRENT FEEDBACK ONE PER SYSTEM is
programmed under the OPTIONS key. Combined
compressor current for each system is displayed.
Oper Data Quick Reference List
The following table is a quick reference list for
information available under the OPER DATA key.
225A • Actual Volts
5
Volts
* Block of information repeats for each system
TABLE 19 – OPERATION DATA
LD14543
Current Feedback One Per System
*System X Condenser Fan Stage
Sys X LLSV & HGSV Status
*System X Run Time
*System X Compressors Status
Current Feedback One Per Unit
Active Remote Control
Evaporator Pump Contacts & Heater Status
Lead System Indicator
Temp Rate & Temp Error
(Leaving Chilled Liquid Control Only)
Cooling Demand Steps
(Return Chilled Liquid Control Only)
Load and Unload Timers
*System X Accumulated Starts
*System X Accumulated Hours
R-407c Only
SYS 2 Cooler Inlet Refrigerant Temp
EEV Only
SYS 2 EEV Output & Suction Superheat
EEV Only
SYS 2 Suction and SAT Suction Temp
System 2 Discharge & Suction Pressure
R-407c Only
SYS 1 Cooler Inlet Refrigerant Temp
EEV Only
SYS 1 EEV Output & Suction Superheat
EEV Only
SYS 1 Suction and SAT Suction Temp
System 1 Discharge & Suction Pressure
Ambient Air Temperature
Leaving & Chilled Liquid Temps
Oper Data Key
Summary of Contents for YCAL0014E Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...JOHNSON CONTROLS 126 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 140: ...JOHNSON CONTROLS 140 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM8 1020 5 6 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM8 1020 5 6 LD08855 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM8 1020 161 5 6 ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM8 1020 5 6 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM8 1020 5 6 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM8 1020 5 6 ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM8 1020 5 6 ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM8 1020 5 6 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM8 1020 5 6 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM8 1020 5 6 ...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 NM8 1020 5 6 ...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 NM8 1020 5 6 LD08833 ...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 NM8 1020 5 6 ...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 NM8 1020 5 6 ...
Page 189: ...JOHNSON CONTROLS 189 FORM 150 62 NM8 1020 5 6 ...
Page 191: ...JOHNSON CONTROLS 191 FORM 150 62 NM8 1020 5 6 ...
Page 195: ...JOHNSON CONTROLS 195 FORM 150 62 NM8 1020 5 6 ...
Page 197: ...JOHNSON CONTROLS 197 FORM 150 62 NM8 1020 5 6 ...
Page 199: ...JOHNSON CONTROLS 199 FORM 150 62 NM8 1020 5 6 ...
Page 200: ...JOHNSON CONTROLS 200 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 211: ...JOHNSON CONTROLS 211 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...