JOHNSON CONTROLS
105
FORM 150.62-NM8 (1020)
2
TABLE 21 – PROGRAM KEY LIMITS AND DEFAULTS
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
DISCHARGE PRESSURE CUTOUT
—
200 psig
399 psig
395 psig
13.8 barg
27.5 barg
27.2 barg
SUCTION PRESSURE CUTOUT
WATER COOLING
44.0 psig
70.0 psig
44.0 psig
3.03 barg
4.83 barg
3.03 barg
GLYCOL COOLING
20.0 psig
70.0 psig
44.0 psig
1.38 barg
4.83 barg
3.03 barg
LOW AMBIENT TEMP, CUTOUT
STANDARD
AMBIENT
25.0°F
60.0°F
25.0°F
-3.9°C
15.6°C
-3.9°C
LOW AMBIENT
0°F
60.0°F
25.0°F
-17.8°C
15.6°C
-3.9°C
LEAVING CHILLED LIQUID TEMP
CUTOUT
WATER COOLING
—
—
36.0°F
2.2°C
GLYCOL COOLING
8.0°F
36.0°F
36.0°F
-13.3°C
2.2°C
2.2°C
ANTI-RECYCLE TIMER
—
300 sec.
600 sec.
600 sec.
FAN CONTROL ON PRESSURE
—
225 psig
260 psig
240 psig
15.5 barg
17.9 barg
16.5 barg
FAN DIFFERENTIAL OFF PRESSURE
—
50 psig
100 PSID*
80 PSID
3.45 barg
6.89 barg*
5.52 barg
TOTAL NUMBER OF COMPRESSOR
SINGLE SYSTEM
2
3
3
TWO SYSTEM
4
6
6
NUMBER OF FANS PER SYSTEM
YCAL 0090
-YCAL0134 ONLY
3
4
3
UNIT/SYSTEM TRIP VOLTS
CURRENT
FEEDBACK
OPTION ENABLED.
ONE PER UNIT
0.5
4.5
2
REMOTE UNIT ID
—
0
7
0
SYSTEM 1 SUPERHEAT SETPOINT
EEV
10.0°F
15.0°F
12.0°F
5.5°C
8.3°C
6.6°C
SYSTEM 2 SUPERHEAT SETPOINT
EEV
10.0°F
15.0°F
12.0°F
5.5°C
8.3°C
6.6°C
* The minimum discharge pressure allowed is 160 psig. The
Fan Differential OFF Pressure
will be lowered to prevent going below 160 psig
based on where the Fan Control ON Pressure is programmed.
Summary of Contents for YCAL0014E Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...JOHNSON CONTROLS 126 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 140: ...JOHNSON CONTROLS 140 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM8 1020 5 6 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM8 1020 5 6 LD08855 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM8 1020 161 5 6 ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM8 1020 5 6 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM8 1020 5 6 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM8 1020 5 6 ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM8 1020 5 6 ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM8 1020 5 6 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM8 1020 5 6 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM8 1020 5 6 ...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 NM8 1020 5 6 ...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 NM8 1020 5 6 LD08833 ...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 NM8 1020 5 6 ...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 NM8 1020 5 6 ...
Page 189: ...JOHNSON CONTROLS 189 FORM 150 62 NM8 1020 5 6 ...
Page 191: ...JOHNSON CONTROLS 191 FORM 150 62 NM8 1020 5 6 ...
Page 195: ...JOHNSON CONTROLS 195 FORM 150 62 NM8 1020 5 6 ...
Page 197: ...JOHNSON CONTROLS 197 FORM 150 62 NM8 1020 5 6 ...
Page 199: ...JOHNSON CONTROLS 199 FORM 150 62 NM8 1020 5 6 ...
Page 200: ...JOHNSON CONTROLS 200 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 211: ...JOHNSON CONTROLS 211 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...