JOHNSON CONTROLS
133
FORM 150.62-NM8 (1020)
4
Analog Inputs – Pressure
Refer to the unit wiring diagram.
Pressure inputs are
connected to the I/O Board on plugs J7 and J9. These
analog inputs represent varying dc signals corresponding
to varying pressures. All voltages are in reference to the
unit case (ground).
System 1 discharge and suction pressures will be
connected to J7 of the I/O Board. System 2 discharge
and suction pressure transducers will be connected to
J9 of the I/O Board.
The discharge transducers are optional on all units except
the YCAL0090 through YCAL0134. If the discharge
transducers are not installed, no connections are made
to the I/O Board and the discharge pressure readout on
the display would be zero.
The suction pressure transducers are optional on
YCAL0014 through YCAL0060. If the suction
transducers are not installed, a mechanical low pressure
switch will be installed in its place, and the suction
pressure readout on the display will be 0 psig when the
low pressure switch is open, and 200 psig (13.79 barg)
when the low pressure switch is closed.
The discharge transducers have a range from 0 to 400
psig. The output will be linear from .5VDC to 4.5VDC
over the 400 psig (27.5 barg) range. Following is the
formula that can be used to verify the voltage output of
the transducer. All voltage reading are in reference to
ground (unit case).
V = (Pressure in psig x .01) + .5
or
V = (Pressure in barg x .145) + .5
where V = dc voltage output
Pressure = pressure sensed by transducer
The I/O Board connections for the Discharge
Transducers:
System 1 Discharge Transducer
J7-6 = +5VDC regulated supply to transducer.
J7-11 = VDC input signal to the I/O Board.
See
the formula above for voltage readings
that correspond to specific discharge
pressures.
J7-7 = +5VDC return
J7-2 = drain (shield connection = 0VDC)
System 2 Discharge Transducer
J9-6 = +5VDC regulated supply to transducer.
J9-11 = VDC input signal to the I/O Board.
See the
formula above for voltage readings that correspond
to specific discharge pressures.
J9-7 = +5VDC return
J9-2 = drain (shield connection = 0VDC)
The suction transducers have a range from 0 to 200 psig
(13.79 barg). The output will be linear from .5VDC to
4.5VDC over the 200 psig (13.79 barg) range. Following
is a formula that can be used to verify the voltage output
of the transducer. All voltage reading are in reference to
ground (unit case).
V = (Pressure in psig x .02) + .5
or
V = (Pressure in barg x .29) + .5
Where V = dc voltage input to microprocessor
Pressure = pressure sensed by transducer
Following are the I/O Board connections for the Suction
Transducer:
System 1 Suction Transducer
J7-5 = +5VDC regulated supply to transducer.
J7-10 = VDC input signal to the I/O Board. (
See
the formula above for voltage readings that
correspond to specific suction pressures.)
J7-9 = +5VDC return
J7-1 = drain (shield connection = 0VDC)
System 2 Suction Transducer
J9-5 = +5VDC regulated supply to transducer.
J9-10 = VDC input signal to the I/O Board.
(See
the formula above for voltage readings that
correspond to specific suction pressures.)
J9-9 = +5VDC return
J9-1 = drain (shield connection = 0VDC)
If the optional Suction Transducer is not used on the
YCAL0014 through YCAL0060, a Low Pressure switch
will be used. Following are the I/O Board connections
for the Low Pressure switch.
Summary of Contents for YCAL0014E Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...JOHNSON CONTROLS 126 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 140: ...JOHNSON CONTROLS 140 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM8 1020 5 6 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM8 1020 5 6 LD08855 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM8 1020 161 5 6 ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM8 1020 5 6 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM8 1020 5 6 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM8 1020 5 6 ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM8 1020 5 6 ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM8 1020 5 6 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM8 1020 5 6 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM8 1020 5 6 ...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 NM8 1020 5 6 ...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 NM8 1020 5 6 LD08833 ...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 NM8 1020 5 6 ...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 NM8 1020 5 6 ...
Page 189: ...JOHNSON CONTROLS 189 FORM 150 62 NM8 1020 5 6 ...
Page 191: ...JOHNSON CONTROLS 191 FORM 150 62 NM8 1020 5 6 ...
Page 195: ...JOHNSON CONTROLS 195 FORM 150 62 NM8 1020 5 6 ...
Page 197: ...JOHNSON CONTROLS 197 FORM 150 62 NM8 1020 5 6 ...
Page 199: ...JOHNSON CONTROLS 199 FORM 150 62 NM8 1020 5 6 ...
Page 200: ...JOHNSON CONTROLS 200 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 211: ...JOHNSON CONTROLS 211 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...