Startup
Panel Checks
(Power On – Both Unit Switch Off)
1.
Apply 3-phase power and verify its value. Voltage
imbalance should be no more than 2% of the
average voltage.
2.
Apply 120VAC and verify its value on the terminal
block in the Power Panel. Make the measurement
between terminals 5 and 2 of CTB2. The voltage
should be 120VAC plus or minus 10%.
3.
Program/verify the Cooling Setpoints, Program
Setpoints, and unit Options. Record the values in
Table 17
(see information on Setpoints and Unit
keys in Section 2 of this IOM for programming
instruction).
4.
Put the unit into Service Mode
(as described
under Section 4 Service and Troubleshooting )
and cycle each condenser fan to ensure proper
rotation.
5.
Prior to this step, turn system 2 off
(if applicable
–refer to Option 2 under Unit Key in Section
2 of this IOM for more information on system
switches.)
Connect a manifold gauge to system
1 suction and discharge service valves.
Place the Unit Switch in the control panel to the
ON position.
As each compressor cycles
ON
, ensure
that the discharge pressure rises and
the suction pressure decreases.
If this does not occur, the compressor being tested
is operating in the reverse direction and must be
corrected. After verifying proper compressor
rotation, turn the Unit Switch to OFF.
This unit uses scroll compressors
which can only operate in one direc
-
tion. Failure to observe this will lead
to compressor failure.
6.
YCAL0040 through YCAL0134 units only – Turn
system
1 off and system 2 ON
(refer to Option 2
under Unit Key in Section 2 of this IOM for more
information on system switches.)
Place the Unit Switch in the control panel to the
ON position.
As each compressor cycles ON, ensure
that the discharge pressure rises and
the suction pressure decreases.
If this does not occur, the compressor being tested
is operating in the reverse direction and must be
corrected. After verifying proper compressor
rotation, turn the Unit Switch to “OFF.”
OPTIONS
Display Language
Sys 1 Switch
Sys 2 Switch
Chilled Liquid
* Ambient Control
Local/Remote Mode
Control Mode
Display Units
* Lead/Lag Control
* Fan Control
Manual Override
Current Feedback
** Soft Start
** Unit Type
** Refrigerant Type
** Expansion Valve Type
COOLING SETPOINTS
Cooling Setpoint
Range
EMS-PWM Max. Setpoint
PROGRAM
Discharge Pressure Cutout
Suct. Pressure Cutout
Low Amb. Temp. Cutout
Leaving Liquid Temp. Cutout
Anti-Recycle Time
Fan Control ON Pressure
Fan Differential OFF Pressure
Total # of Compressors
* Number of Fans/System
* Unit/Sys Voltage
Unit ID
* Sys 1 Superheat Setpoint
* Sys 2 Superheat Setpoint
* Not on all models
** Viewable only
TABLE 17 - SETPOINTS ENTRY LIST
Summary of Contents for YCAL0014E Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...JOHNSON CONTROLS 126 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 140: ...JOHNSON CONTROLS 140 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM8 1020 5 6 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM8 1020 5 6 LD08855 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM8 1020 161 5 6 ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM8 1020 5 6 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM8 1020 5 6 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM8 1020 5 6 ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM8 1020 5 6 ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM8 1020 5 6 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM8 1020 5 6 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM8 1020 5 6 ...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 NM8 1020 5 6 ...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 NM8 1020 5 6 LD08833 ...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 NM8 1020 5 6 ...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 NM8 1020 5 6 ...
Page 189: ...JOHNSON CONTROLS 189 FORM 150 62 NM8 1020 5 6 ...
Page 191: ...JOHNSON CONTROLS 191 FORM 150 62 NM8 1020 5 6 ...
Page 195: ...JOHNSON CONTROLS 195 FORM 150 62 NM8 1020 5 6 ...
Page 197: ...JOHNSON CONTROLS 197 FORM 150 62 NM8 1020 5 6 ...
Page 199: ...JOHNSON CONTROLS 199 FORM 150 62 NM8 1020 5 6 ...
Page 200: ...JOHNSON CONTROLS 200 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 211: ...JOHNSON CONTROLS 211 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...