Condenser Fan Control on models YCAL0090 through
YCAL0104 will always be by discharge pressure. The
ON pressure and the differential OFF pressure are
programmable under the PROGRAM key.
CONDENSER FAN CONTROL (CONT'D)
YCAL0090 – YCAL0104
The following
figures and tables
outline fan sequencing
for the various models. These models are equipped to
operate to 0°F ambient as a standard.
FAN #3
FAN #5
FAN #7
FAN #4
FAN #6
FAN #8
FIG. 10 – YCAL0090 THROUGH YCAL0104 FAN LOCATION
LD07828A
TABLE 30 – YCAL0090 - YCAL0104 CONDENSER FAN CONTROL
FAN
STAGE
ON
OFF
CONTACTOR
I/O BOARD
OUTPUT
FAN #
SYS 1 SYS 2
SYS 1
SYS 2
SYS 1 SYS 2
1
1 FAN
FWD
DP > Fan Ctrl On
Press
DP < Fan Ctrl On Press
– (Diff. Press.)
10M
14M
TB7-8
TB10-8
7
8
2
2 FANS
FWD
DP > Fan Ctrl On
Press + 20 psig (1.38
bars)
DP < Fan Ctrl On Press.) –
[(Diff Press.) + 20
psig (1.38
bars)]
9M &
10M
13M &
14M
TB7-8 &
TB7-9
TB10-8 &
TB10-9
5 & 7 6 & 8
3
3 FANS
FWD
DP > Fan Ctrl On
Press + 40 psig (2.76
bars)
DP < Fan Ctrl On Press.) –
[(Diff Press.) + 40
psig (2.76
bars)]
8M, 9M
& 10M
12M,
13M &
14M
TB7-8,
TB7-9
&
TB7-10
TB10-8,
TB10-9 &
TB10-10
3, 5
& 7
4, 6
& 8
Summary of Contents for YCAL0014E Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...JOHNSON CONTROLS 126 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 140: ...JOHNSON CONTROLS 140 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM8 1020 5 6 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM8 1020 5 6 LD08855 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM8 1020 161 5 6 ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM8 1020 5 6 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM8 1020 5 6 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM8 1020 5 6 ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM8 1020 5 6 ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM8 1020 5 6 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM8 1020 5 6 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM8 1020 5 6 ...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 NM8 1020 5 6 ...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 NM8 1020 5 6 LD08833 ...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 NM8 1020 5 6 ...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 NM8 1020 5 6 ...
Page 189: ...JOHNSON CONTROLS 189 FORM 150 62 NM8 1020 5 6 ...
Page 191: ...JOHNSON CONTROLS 191 FORM 150 62 NM8 1020 5 6 ...
Page 195: ...JOHNSON CONTROLS 195 FORM 150 62 NM8 1020 5 6 ...
Page 197: ...JOHNSON CONTROLS 197 FORM 150 62 NM8 1020 5 6 ...
Page 199: ...JOHNSON CONTROLS 199 FORM 150 62 NM8 1020 5 6 ...
Page 200: ...JOHNSON CONTROLS 200 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 211: ...JOHNSON CONTROLS 211 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...