035-14841-000 Rev. A (0701)
Unitary Products Group
9
DISCONNECT SWITCH BRACKET
A special bracket for mounting a field-supplied disconnect
switch is provided in each unit. The bracket is shipped inside
the blower compartment taped to the top of the blower
housing.
Install the bracket on the left hand side of the unit as shown in
Figure 5. Several existing screws at the top of the unit and
one screw approximately midway down from the top will be
used for mounting the bracket. Screws should be loosened
only - NOT REMOVED. Matching holes in the bracket have
elongated keyways allowing easy installation. Re-tighten
screws after bracket is in place to ensure panels will remain
leak tight.
Electric heaters are available as field-installed accessories.
Refer to Form 530.18-N7.1V for installation instruction. These
UL approved heaters are located within the central compart-
ment of the unit (see Figure 5 for access panel) with the heat-
ing elements extending into the supply air chamber.
The heaters are wired for a single point power supply. Power
supply need only be brought into the single point terminal
block and thermostat wiring to the low voltage terminal strip
located in the upper portion of the unit control box.
Fuses are supplied, where required, by the factory. Some KW
sizes require fuses and others do not. Refer to the accessory
instruction for electrical data.
FIGURE 4 : ENTHALPY SET POINT ADJUSTMENT
Summary of Contents for SUNLINE ULTRA D1HG 036
Page 10: ...035 14841 000 Rev A 0701 10 Unitary Products Group FIGURE 5 DIMENSIONS CLEARANCES 3 4 5 TONS...
Page 18: ...035 14841 000 Rev A 0701 18 Unitary Products Group...
Page 19: ...035 14841 000 Rev A 0701 Unitary Products Group 19...
Page 20: ...035 14841 000 Rev A 0701 20 Unitary Products Group...
Page 21: ...035 14841 000 Rev A 0701 Unitary Products Group 21...
Page 22: ...035 14841 000 Rev A 0701 22 Unitary Products Group...
Page 23: ...035 14841 000 Rev A 0701 Unitary Products Group 23...