035-14841-000 Rev. A (0701)

2

Unitary Products Group

IMPROPER INSTALLATION MAY CREATE A
CONDITION WHERE THE OPERATION OF THE
PRODUCT COULD CAUSE PERSONAL INJURY
OR PROPERTY DAMAGE.

IMPROPER INSTALLATION, ADJUSTMENT,
ALTERATION, SERVICE OR MAINTENANCE
CAN CAUSE INJURY OR PROPERTY DAMAGE.
REFER TO THIS MANUAL FOR ASSISTANCE
OR ADDITIONAL INFORMATION, CONSULT A
QUALIFIED INSTALLER, SERVICE AGENCY OR
THE GAS SUPPLIER.

THIS PRODUCT MUST BE INSTALLED IN
STRICT COMPLIANCE WITH THE ENCLOSED
INSTALLATION INSTRUCTIONS AND ANY
APPLICABLE LOCAL, STATE, AND NATIONAL
CODES INCLUDING BUT NOT LIMITED TO,
BUILDING, ELECTRICAL AND MECHANICAL
CODES.

The furnace area must not be used as a broom
closet or for any other storage purposes, as a fire
hazard bay be created. Never store items such as
the following on, near or in contact with the fur-
nace.

1.

Spray or aerosol cans, rags, brooms, dust mops, vac-
uum cleaners or other cleaning tools.

2.

Soap powders, bleaches, waxes or other cleaning
compounds; plastic items or containers; gasoline, kero-
sene, cigarette lighter fluid, dry cleaning fluids or other
volatile fluid.

3.

Paint thinners and other painting compounds.

4.

Paper bags, boxes or other paper products

Never operate the furnace with the blower door
removed. To do so could result in serious personal
injury and/or equipment damage.

WARNING

CAUTION

WARNING

CONTENTS

GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
RENEWAL PARTS: . . . . . . . . . . . . . . . . . . . . . . . . . . 3
APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 4
LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
RIGGING AND HANDLING . . . . . . . . . . . . . . . . . . . . 5
CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CONDENSATE DRAIN . . . . . . . . . . . . . . . . . . . . . . . 5
SERVICE ACCESS . . . . . . . . . . . . . . . . . . . . . . . . . . 6
THERMOSTAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
POWER AND CONTROL WIRING . . . . . . . . . . . . . . 6
COMPRESSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
OPTIONAL ECONOMIZER RAIN HOOD . . . . . . . . . 7
DISCONNECT SWITCH BRACKET . . . . . . . . . . . . . 9
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
COOLING SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . 15
PRELIMINARY OPERATION COOLING . . . . . . . . 15
COOLING SEQUENCE OF OPERATION . . . . . . . . 15
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . 15
HEATING SEQUENCE OF OPERATION . . . . . . . . 15
TWO-STAGE HEATING: . . . . . . . . . . . . . . . . . . . . . 16
HEAT ANTICIPATOR SETPOINTS . . . . . . . . . . . . 16
CHECKING SUPPLY AIR CFM . . . . . . . . . . . . . . . . 16
BELT-DRIVE BLOWER . . . . . . . . . . . . . . . . . . . . . . 16
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
NORMAL MAINTENANCE . . . . . . . . . . . . . . . . . . . 17

LIST OF FIGURES

CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 5
RECOMMENDED DRAIN PIPING . . . . . . . . . . . . . . 5
ECOMONIZER RAIN HOOD ASSEMBLY (OPTION) 7
ENTHALPY SET POINT ADJUSTMENT . . . . . . . . . 9
DIMENSIONS & CLEARANCES - 3, 4 & 5 TONS . 10
TYPICAL FIELD WIRING . . . . . . . . . . . . . . . . . . . . 11
BELT ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . 16
PRESSURE DROP ACROSS A DRY

EVAPORATOR COIL VS. SUPPLY AIR CFM,

WITHOUT AIR FILTERS . . . . . . . . . . . . . . . . . . . . . 17

LIST OF TABLES

PHYSICAL DATA ....................................................... 6
SUPPLY AIR PERFORMANCE - 3-TON ................. 12
SUPPLY AIR PERFORMANCE - 4 TON ..................12
SUPPLY AIR PERFORMANCE - 5 TON ..................13
STATIC RESISTANCES .......................................... 14
MOTOR AND DRIVE DATA- Belt-Drive Blower ....... 14
ELECTRICAL DATA- Basic Unit .............................. 14
HEAT ANTICIPATOR SETTING .............................. 16
BELT DRIVE SUPPLY AIR ADJUSTMENT
MOTOR PULLEY ADJUSTMENT ............................ 16

Summary of Contents for SUNLINE ULTRA D1HG 036

Page 1: ...WITCH BRACKET 9 COOLING SYSTEM 15 PRELIMINARY OPERATION COOLING 15 COOLING SEQUENCE OF OPERATION 15 SAFETY CONTROLS 15 HEATING SEQUENCE OF OPERATION 15 TWO STAGE HEATING 16 HEAT ANTICIPATOR SETPOINTS...

Page 2: ...Never operate the furnace with the blower door removed To do so could result in serious personal injury and or equipment damage WARNING CAUTION WARNING CONTENTS GENERAL 3 INSPECTION 3 REFERENCE 3 RENE...

Page 3: ...30 18 N2 11V Low NOx Accessory 530 18 N8 2V High Altitude Accy Natural Gas 530 18 N8 3V High Altitude Accy Propane 530 18 N8 4V Gas Piping Accessory 530 18 N8 12V Propane Conversion Accessory 690 15 N...

Page 4: ...r slab should be used The thickness and size of the pad or slab used should meet local codes and unit weight Do not tie the slab to the building foundation 4 Roof structures must be able to support th...

Page 5: ...connec tions on the unit Refer to Figure 5 for information concerning side and bottom supply and return air duct openings FILTERS 1 filters are supplied with each unit 2 replacement filters may be us...

Page 6: ...t must be wired with a separate branch circuit fed directly from the meter panel and properly protected Refer to Figure 6 for typical field wiring and to the appropriate unit wiring diagram for contro...

Page 7: ...n Step 2 to the sensor as follows Wire 73 to terminal Wire 74 to terminal S 5 Assemble the LH and RH side plates to the top cover 2 screws each side to form the hood Apply gasketing to the flange surf...

Page 8: ...enthalpy economizer carefully turn the set point adjusting screw fully clockwise past the D setting 10 To check that the damper blades move smoothly without binding carefully turn the minimum position...

Page 9: ...tighten screws after bracket is in place to ensure panels will remain leak tight Electric heaters are available as field installed accessories Refer to Form 530 18 N7 1V for installation instruction T...

Page 10: ...035 14841 000 Rev A 0701 10 Unitary Products Group FIGURE 5 DIMENSIONS CLEARANCES 3 4 5 TONS...

Page 11: ...L E C T R I C H E A T A C C E S S O R Y W I T H T W O S T A G E S O F H E A T U S E T H E R M O S T A T 2 T H 0 4 7 1 0 2 4 A D D J U M P E R R C R H Y 1 Y 2 W 1 W 2 G L E D 1 L E D 2 C O M A 1 A 2 T...

Page 12: ...er to the Static Resistances Table for resistance values on applications other than gas electric units with side duct air flows TABLE 4 SUPPLY AIR PERFORMANCE 4 TON 4 TON GAS HEAT VALUES SHOWN 230 460...

Page 13: ...860 950 905 988 940 1022 970 1700 884 815 925 850 964 880 1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 UNIT SIZE MBH AIR FLOW CFM Available External Static Pressure IWG 0...

Page 14: ...ANGE RPM MOTOR ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT HP RPM FRAME SIZE SERVICE FACTOR PITCH DIA IN BORE PITCH DIA IN BORE PITCH LENGTH DESIGNATIONS DHG 036 790 1 120 1 1 2 1 725 56 1 15 2 4...

Page 15: ...Jumper wire J1 must be removed Refer to unit wiring diagram After the thermostat is satisfied and opens the blower will continue to run for a short time All other components will stop SAFETY CONTROLS...

Page 16: ...tension on the belts should be adjusted as shown in Figure 7 Start the supply air blower motor Adjust the resistances in both the supply and the return air duct systems to balance the air distribution...

Page 17: ...AL MAINTENANCE FILTERS Inspect once a month Replace disposable or clean permanent type as necessary DO NOT replace perma nent type with disposable MOTORS Indoor fan and outdoor fan motors are perma ne...

Page 18: ...035 14841 000 Rev A 0701 18 Unitary Products Group...

Page 19: ...035 14841 000 Rev A 0701 Unitary Products Group 19...

Page 20: ...035 14841 000 Rev A 0701 20 Unitary Products Group...

Page 21: ...035 14841 000 Rev A 0701 Unitary Products Group 21...

Page 22: ...035 14841 000 Rev A 0701 22 Unitary Products Group...

Page 23: ...035 14841 000 Rev A 0701 Unitary Products Group 23...