035-14841-000 Rev. A (0701)

12

Unitary Products Group

TABLE 3: SUPPLY AIR PERFORMANCE - 3-TON

3 TON GAS HEAT VALUES SHOWN @ 230/460 VOLTS - SIDE DUCT CONNECTIONS

UNIT

SIZE

(MBH)

AIR FLOW

CFM

Avail able External Static Pres sure - IWG

*

0.20

0.30

0.40

0.50

0.60

0.70

0.80

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

036

2000

843

860

880

925

919

1005

956

1065

993

1145

1030

1195

1067

1235

1900

817

775

854

850

893

920

930

995

970

1065

1008

1125

1046

1170

1800

790

700

828

760

867

840

906

905

944

980

985

1040

1025

1100

1700

-

-

802

670

840

745

881

815

920

900

961

970

1001

1030

1600

-

-

-

-

818

665

858

740

898

820

940

890

980

950

1500

-

-

-

-

-

-

842

695

882

755

922

835

962

895

1400

-

-

-

-

-

-

833

650

867

705

904

765

942

820

1300

-

-

-

-

-

-

-

-

858

665

893

725

932

785

1200

-

-

-

-

-

-

-

-

847

640

880

680

916

730

UNIT

SIZE

(MBH)

AIR FLOW

CFM

Avail able External Static Pres sure - IWG*

0.90

1.00

1.10

1.20

1.30

1.40

1.50

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

036

2000

1103

1270

-

-

-

-

-

-

-

-

-

-

-

-

1900

1085

1210

-

-

-

-

-

-

-

-

-

-

-

-

1800

1064

1145

1102

1180

-

-

-

-

-

-

-

-

-

-

1700

1040

1075

1081

1115

1121

1140

-

-

-

-

-

-

-

-

1600

1020

1005

1060

1050

1100

1085

-

-

-

-

-

-

-

-

1500

1003

945

1044

995

1086

1035

-

-

-

-

-

-

-

-

1400

982

880

1024

920

1067

965

1107

1000

-

-

-

-

-

-

1300

970

835

1010

870

1053

920

1099

960

-

-

-

-

-

-

1200

953

780

992

815

1034

855

1080

905

-

-

-

-

-

-

NOTE: For 208 Volts, multiply values by 0.95.

*.

Includes allowances for a wet evaporator coil, 1” filters and gas-fired heat exchangers. Refer to the Static Resistances Table for
resistance values on applications other than gas / electric units with side duct air flows.

TABLE 4: SUPPLY AIR PERFORMANCE - 4 TON

4 TON GAS HEAT VALUES SHOWN @ 230/460 VOLTS - SIDE DUCT CONNECTIONS

UNIT

SIZE

(MBH)

AIR FLOW

CFM

Available External Static Pressure - IWG

*

0.20

0.30

0.40

0.50

0.60

0.70

0.80

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

048

2000

843

860

880

925

919

1005

956

1065

993

1145

1030

1195

1067

1235

1900

817

775

854

850

893

920

930

995

970

1065

1008

1125

1046

1170

1800

790

700

828

760

867

840

906

905

944

980

985

1040

1025

1100

1700

-

-

802

670

840

745

881

815

920

900

961

970

1001

1030

1600

-

-

-

-

818

665

858

740

898

820

940

890

980

950

1500

-

-

-

-

-

-

842

695

882

755

922

835

962

895

1400

-

-

-

-

-

-

833

650

867

705

904

765

942

820

1300

-

-

-

-

-

-

-

-

858

665

893

725

932

785

1200

-

-

-

-

-

-

-

-

847

640

880

680

916

730

UNIT

SIZE

(MBH)

AIR FLOW

CFM

Available External Static Pressure - IWG*

0.90

1.00

1.10

1.20

1.30

1.40

1.50

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

048

2000

1103

1270

-

-

-

-

-

-

-

-

-

-

-

-

1900

1085

1210

-

-

-

-

-

-

-

-

-

-

-

-

1800

1064

1145

1102

1180

-

-

-

-

-

-

-

-

-

-

1700

1040

1075

1081

1115

1121

1140

-

-

-

-

-

-

-

-

1600

1020

1005

1060

1050

1100

1085

-

-

-

-

-

-

-

-

1500

1003

945

1044

995

1086

1035

-

-

-

-

-

-

-

-

1400

982

880

1024

920

1067

965

1107

1000

-

-

-

-

-

-

1300

970

835

1010

870

1053

920

1099

960

-

-

-

-

-

-

1200

953

780

992

815

1034

855

1080

905

-

-

-

-

-

-

NOTE: For 208 Volts, multiply values by 0.95.

*.

Includes allowances for a wet evaporator coil, 1” filters and gas-fired heat exchangers. Refer to the Static Resistances Table for
resistance values on applications other than gas / electric units with side duct air flows

Summary of Contents for SUNLINE ULTRA D1HG 036

Page 1: ...WITCH BRACKET 9 COOLING SYSTEM 15 PRELIMINARY OPERATION COOLING 15 COOLING SEQUENCE OF OPERATION 15 SAFETY CONTROLS 15 HEATING SEQUENCE OF OPERATION 15 TWO STAGE HEATING 16 HEAT ANTICIPATOR SETPOINTS...

Page 2: ...Never operate the furnace with the blower door removed To do so could result in serious personal injury and or equipment damage WARNING CAUTION WARNING CONTENTS GENERAL 3 INSPECTION 3 REFERENCE 3 RENE...

Page 3: ...30 18 N2 11V Low NOx Accessory 530 18 N8 2V High Altitude Accy Natural Gas 530 18 N8 3V High Altitude Accy Propane 530 18 N8 4V Gas Piping Accessory 530 18 N8 12V Propane Conversion Accessory 690 15 N...

Page 4: ...r slab should be used The thickness and size of the pad or slab used should meet local codes and unit weight Do not tie the slab to the building foundation 4 Roof structures must be able to support th...

Page 5: ...connec tions on the unit Refer to Figure 5 for information concerning side and bottom supply and return air duct openings FILTERS 1 filters are supplied with each unit 2 replacement filters may be us...

Page 6: ...t must be wired with a separate branch circuit fed directly from the meter panel and properly protected Refer to Figure 6 for typical field wiring and to the appropriate unit wiring diagram for contro...

Page 7: ...n Step 2 to the sensor as follows Wire 73 to terminal Wire 74 to terminal S 5 Assemble the LH and RH side plates to the top cover 2 screws each side to form the hood Apply gasketing to the flange surf...

Page 8: ...enthalpy economizer carefully turn the set point adjusting screw fully clockwise past the D setting 10 To check that the damper blades move smoothly without binding carefully turn the minimum position...

Page 9: ...tighten screws after bracket is in place to ensure panels will remain leak tight Electric heaters are available as field installed accessories Refer to Form 530 18 N7 1V for installation instruction T...

Page 10: ...035 14841 000 Rev A 0701 10 Unitary Products Group FIGURE 5 DIMENSIONS CLEARANCES 3 4 5 TONS...

Page 11: ...L E C T R I C H E A T A C C E S S O R Y W I T H T W O S T A G E S O F H E A T U S E T H E R M O S T A T 2 T H 0 4 7 1 0 2 4 A D D J U M P E R R C R H Y 1 Y 2 W 1 W 2 G L E D 1 L E D 2 C O M A 1 A 2 T...

Page 12: ...er to the Static Resistances Table for resistance values on applications other than gas electric units with side duct air flows TABLE 4 SUPPLY AIR PERFORMANCE 4 TON 4 TON GAS HEAT VALUES SHOWN 230 460...

Page 13: ...860 950 905 988 940 1022 970 1700 884 815 925 850 964 880 1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 UNIT SIZE MBH AIR FLOW CFM Available External Static Pressure IWG 0...

Page 14: ...ANGE RPM MOTOR ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT HP RPM FRAME SIZE SERVICE FACTOR PITCH DIA IN BORE PITCH DIA IN BORE PITCH LENGTH DESIGNATIONS DHG 036 790 1 120 1 1 2 1 725 56 1 15 2 4...

Page 15: ...Jumper wire J1 must be removed Refer to unit wiring diagram After the thermostat is satisfied and opens the blower will continue to run for a short time All other components will stop SAFETY CONTROLS...

Page 16: ...tension on the belts should be adjusted as shown in Figure 7 Start the supply air blower motor Adjust the resistances in both the supply and the return air duct systems to balance the air distribution...

Page 17: ...AL MAINTENANCE FILTERS Inspect once a month Replace disposable or clean permanent type as necessary DO NOT replace perma nent type with disposable MOTORS Indoor fan and outdoor fan motors are perma ne...

Page 18: ...035 14841 000 Rev A 0701 18 Unitary Products Group...

Page 19: ...035 14841 000 Rev A 0701 Unitary Products Group 19...

Page 20: ...035 14841 000 Rev A 0701 20 Unitary Products Group...

Page 21: ...035 14841 000 Rev A 0701 Unitary Products Group 21...

Page 22: ...035 14841 000 Rev A 0701 22 Unitary Products Group...

Page 23: ...035 14841 000 Rev A 0701 Unitary Products Group 23...

Page 24: ...to change without notice Printed in U S A 035 14841 000 Rev A 0701 Copyright by Unitary Products Group 2000 All rights reserved Supersedes 530 23 N1Y 0500 Unitary 5005 Norman Product York OK Group Dri...

Reviews: