8
YORK INTERNATIONAL
LD02071
NOTES:
1. Clearances – Minimum YORK clearances to prevent condenser air recirculation and faulty operation of units are as follows:
Side-to-wall 8'–0" * Rear-to-wall 8'–0" * Control Panel End-to-wall 5'–0" Top 50'–0" Distance between adjacent units 12'–0"
Failure to heed minimum clearances may result in reduced system performance, nuisance shutdowns and servicing
problems.
* No more than one wall can be higher than the top of the unit.
The area within the clearances shown above and area under the unit must be kept clear of all obstructions that would impede free air flow
to the unit. In installations where winter operation is intended and snow accumulations are expected, additional unit height must be provided
to insure full air flow.
2. VIBRATION ISOLATORS (optional) will increase overall height of unit by approx. 6".
3. Drawings not to scale and are for planning purposes only. Contact nearest YORK office for detail drawings.
DIMENSIONS
MODEL
WEIGHT DISTRIBUTIONS (LBS.)
NOZZLE SIZE
YEA
A
B
C
D
E
INLET/OUTLET
Z88DR6
2194
1911
2202
1982
1'–4"
6
J44DR7
2602
2318
2341
2121
1'–4"
6
J44DR6
2606
2322
2345
2125
1'–4"
6
J55DR7
2669
2385
2372
2151
1'–4"
6
J44HT6
2690
2406
2569
2349
1'–5"
8
J55HT7
2754
2470
2586
2365
1'–5"
8
J54ES6
2681
2371
2365
2136
1'–4"
6
J65ES7
2771
2444
2403
2167
1'–4"
6
J55HT8
2798
2494
2625
2389
1'–5"
8
J66HT9
2930
2626
2697
2461
1'–5"
8
J65HT8
2871
2521
2649
2389
1'–5"
8
J76HT9
2990
2643
2709
2459
1'–5"
8
J66MT8
3008
2703
3200
2694 1'–6-1/2"
8
J77MT9
3127
2822
3261
3024 1'–6-1/2"
8