
80
YORK INTERNATIONAL
5. Further minor adjustment may be necessary to be
certain that the valve opens fully before the tempera-
ture point at which the compressor stops due to a
fall in Return or Leaving Water Temp.
6. Repeat this procedure on the other system.
NOTE: Hot gas should not be considered as an addi-
tional step of unloading when programming the
number of steps of loading/unloading.
FIELD INSTALLATION
If it becomes necessary to field install the Hot Gas (Load-
minder) Option, two kits are required. Order the kit from
the list below:
KIT, HOT GAS BYPASS (LOADMINDER)
MODEL
PART NUMBERS
NUMBER
STANDARD UNIT
UNIT WITH
REMOTE COOLER
YCAJ88DR6
375-04528-004
375-04529-004
YCAJ44DR7
375-04528-001
375-04529-001
YCAJ44DR6
375-04528-001
375-04529-001
YCAJ55DR7
375-04528-001
375-04529-001
YCAJ44HT6
375-04528-001
375-04529-001
YCAJ44HT7
375-04528-001
375-04529-001
YCAJ54ES6
375-04528-001
375-04529-001
YCAJ65ES7
375-04528-002
375-04529-002
YCAJ55HT8
375-04528-001
375-04529-001
YCAJ66HT9
375-04528-003
375-04529-003
YCAJ65HT8
375-04528-002
375-04529-002
YCAJ76HT9
375-04528-003
375-04529-003
YCAJ66MT8
375-04528-003
375-04529-003
YCAJ77MT9
375-04528-003
375-04529-003
In addition, a 471-01232-101 kit must also be ordered.
The 471-01232-101 kit consists of a second Relay Out-
put Board. It is not required if two Relay Boards are al-
ready installed in the control panel.
DISCHARGE PRESSURE READOUT OPTION
The Discharge Pressure Read-out Option P/N 471-
01262-111 allows the user to obtain control panel dis-
plays of discharge pressure. Additionally, other displays
such as fault information will then hold relevant discharge
pressure information useful in diagnosing problems.
The discharge pressure unloading feature also becomes
usable when this option is installed (Page 36) as well as
fan cycling by discharge pressure.
Fan cycling by discharge pressure sometimes becomes
necessary, if ambient temperature cycling of fans causes
low suction pressure faults due to unusual operating condi-
tions or chiller location problems. Fan cycling by discharge
pressure only, allows higher discharge pressures which in
turn raises suction pressure by permitting better operation
of the thermal expansion valve. To convert to discharge pres-
sure cycling, the micro panel must be programmed for DIS-
CHARGE PRESSURE FAN CONTROL (See Page 30).
Fan cycling will operate as indicated in Table 3.
SYS
FAN
CONTACTORS
ON
OFF
1 REV
(Optional
7M
320 PSIG
120 PSIG
1
Low Ambient)
2
6M
340 PSIG
120 PSIG
1 FWD
5M
360 PSIG
140 PSIG
3 REV
(Optional
10M
320 PSIG
120 PSIG
2
Low Ambient)
4
9M
340 PSIG
120 PSIG
3 FWD
8M
360 PSIG
140 PSIG
TABLE 3
FAN CONTROL BY DISCHARGE
PRESSURE
The kit consists of discharge pressure transducers for
each system, wire harnesses, and associated mounting
hardware.
HIGH AMBIENT OPTION
The High Ambient Option consists of two kits, P/Ns
471-01262-111 and 475-04250-000. The option allows
operation of the chiller in ambients up to 115°F. Typi-
cally, standard operation is limited to 105°F. High am-
bient operation is accomplished by discharge pressure
unloading to assure that the chiller does not fault due to
the high pressure cut-out opening during high tempera-
ture operation. A sun shield is also installed on the con-
trol panel to prevent direct sunlight from overheating the
control panel causing subsequent malfunction of the
electro-mechanical and electronic components in the
control panel. Additionally, actual discharge pressure
read-outs can now be obtained from the micro panel.
Discharge Pressure unloading allows the microproces-
sor to unload a compressor when the discharge pres-
sure approaches a point nearing the discharge pressure
cut-out. This assures that the system does not shut down
completely if the cut-out were to open. See Page 35 for
programming the unloading pressure.
Fan cycling by discharge pressure is also available when
this option is installed (See DISCHARGE PRESSURE
READ-OUT OPTION, Page 80), however it is of little use
in areas where ambients are generally high and stan-
dard temperature control of the fans provides good con-
trol and maximum efficiency.