FORM 150.60-NM4
YORK INTERNATIONAL
75
OPTIONS
CONDENSER WATER PUMP CONTACT/RUN
STATUS OPTION
This option provides a dry contact which can be used
to turn on the condenser water pump, other device, or
indicate run status. The contact closes whenever one of
the compressors start.
Connections to this contact can be made on Terminals
21 and 22 of TB1 in the power panel. The location of
these terminals is shown in Fig. 29.
fill the compressor crankcase, connect the delivery
tube of the YORK Hand Oil Pump. YORK Part No.
470-10654 or equal to the compressor oil charging
and drain valve. Expel all air from the delivery tube
by pumping it full of oil, allowing a few drips to drip
out before tightening the flare nut to the oil charg-
ing valve. Then open the oil charging valve and pump
oil into the crankcase to the proper level. It is nec-
essary that the suction end of the hand oil pump
be kept submerged under the oil level in the con-
tainer at all times, to avoid entrance of air into the
compressor.
I. Before opening the suction or discharge stop valves,
connect a vacuum pump to the pumpout port in the
discharge stop valve. (Pumpout port is port on valve
stem side of valve). With the vacuum line shutoff
This option utilizes a second Relay Output Board and
associated wiring. The part number for the Field Mounted
Pump Control Kit is 471-01232-101. This kit is not re-
quired if a second Relay Output Board is already installed.
NOTE: Any inductive devices (contactor/relay coil) con-
nected to these contacts must be suppressed
with YORK P/N 031-00808 supplied by others.
Otherwise, nuisance faults may occur.
This section is devoted to options which may be ordered or retrofitted to the unit. Listed below are the options which
are covered in this section.
1. CONDENSER WATER PUMP / RUN STATUS CONTACT OPTION
2. EVAPORATOR WATER PUMP CONTACT OPTION
3. LOW AMBIENT ACCESSORY
4. HOT GAS BYPASS (LOADMINDER) OPTION
5. DISCHARGE PRESSURE READOUT OPTION
6. HIGH AMBIENT OPTION
7. LOCAL PRINTER OPTION
8. OPTIONAL TAMPERPROOF ENCLOSURE (WIRE GRILLE)
9. OPTIONAL DECORATIVE TAMPERPROOF ENCLOSURE (LOUVERED & WIRE GRILLE)
10. OPTIONAL DECORATIVE TAMPERPROOF ENCLOSURE (LOUVERED)
11. BAS INTERFACE OPTION (REMOTE RESET OPTION)
Both controls are included as part
of the PUMP CONTROL KIT
valve open, run the vacuum pump until a vacuum of
at least 1000 microns is reached. Stop the vacuum
pump, close the shut-off valve and open the dis-
charge valve fully before disconnecting the line from
the vacuum pump. Disconnect the vacuum pump
and replace the plug in the pumpout port.
NOTE: If suction or discharge valves are not seated
properly, a 1000 micron vacuum can not be ob-
tained. Do not evacuate for long periods of time.
J. Be sure both discharge and suction stop valves
are open before operating the unit.
4. Suction and Discharge Valves The condition of the
suction and discharge valves should be checked by
YORK service personnel.