
72
YORK INTERNATIONAL
CHECKING SUPERHEAT AND SUBCOOLING
The subcooling should always be checked when charg-
ing the system with refrigerant and/or before setting the
superheat.
When the refrigerant charge is correct, there will be no
bubbles in the liquid sightglass with the system operat-
ing under full load conditions, and there will be 10°F to
15°F subcooled liquid refrigerant leaving the condenser.
An overcharged system should be guarded against. Evi-
dences of overcharge are as follows:
a. If a system is overcharged, the discharge pressure
will be higher than normal. (Normal discharge/
condensing pressure can be found in refrigerant
temperature/pressure chart; use entering air tempera-
ture +30°F for normal condensing temperatures.)
b. The temperature of the liquid refrigerant out of the
condenser should not be more than 15°F less than
the condensing temperature. (The temperature cor-
responding to the condensing pressure from refriger-
ant temperature/pressure chart).
The subcooling temperature should be taken by record-
ing the temperature of the liquid line at the outlet of the
condenser and recording the liquid line pressure at the
liquid stop valve and converting it to a temperature from
temperature/pressure chart.
Example:
LIQUID LINE PRESSURE
202 PSIG converted to
102°F
Minus Liquid Line Temperature
- 87°F
Subcooling =
15°F
Record:
SYS 1
SYS 2
LIQUID LINE PRESSURE:
PSIG
LIQUID LINE TEMPERATURE:
°F
SUBCOOLING:
°F
After the subcooling is set at 10°-15°F the superheat
should be checked.
The superheat should be checked only after steady op-
eration of the chiller has been established, the leaving
chilled liquid has been pulled down to the required tem-
perature, and the unit is running fully loaded. Correct
superheat setting is 10°-12°F.
The superheat is the difference between the actual tem-
perature of the returned refrigerant gas entering the com-
pressor and the temperature corresponding to the suc-
tion pressure as shown in a standard pressure/tem-
perature chart.
Example:
Suction Temperature
44°F
Minus Suction Pressure 60 PSIG
34°F
Converted to Temp. Superheat
10°F
The suction temperature should be taken 6" before the
compressor service valve, and the suction pressure is
taken at the compressor suction service valve.
Record:
SYS 1
SYS 2
SUCTION TEMPERATURE:
PSIG
SUCTION PRESSURE:
°F
SUPERHEAT:
°F
Normally, the thermal expansion valve need not be ad-
justed in the field. If, however, and adjustment is to be
made, the expansion valve adjusting screw should be
turned not more than one turn at a time, allowing suffi-
cient time (approximately 15 minutes) between ad-
justments for the system and the thermal expansion valve
to respond and return to settled operation.
If the unit has been functioning satisfactorily during the
initial operating period, it is ready for continuous opera-
tion.
*
Leak check compressors, fittings, and piping to
assure no leaks are present from improper han-
dling.
NOTES: ___________________________________
_________________________________________
_________________________________________
_________________________________________
_________________________________________
_________________________________________
_________________________________________
_________________________________________
*
START-UP COMPLETE