FORM 150.60-NM4
YORK INTERNATIONAL
15
LD02075
LD02076
LD02077
FIG. 4 – COMPRESSOR MOUNTING PAD
25112A
TYPE & SIZE
MAX. LOAD
SPRING COLOR
DEFL. INS.
LBS. (KG)
( m m )
CP-2-25
900
(408.2)
Red
1.22
(30.9)
CP-2-26
1200
(544.3)
Purple
1.17
(29.7)
CP-2-27
1500
(680.4)
Orange
1.06
(26.9)
CP-2-28
1800
(816.4)
Green
1.02
(25.9)
CP-2-31
2200
(977.9)
Gray
.83
(21.0)
CP-2-32
2600 (1179.3)
White
.74
(18.7)
CP-2-35
3000 (1360.8)
Gold
.70
(17.7)
TYPE & SIZE
MAX. LOAD
SPRING COLOR
DEFL. INS.
LBS. (KG)
( m m )
CP-4-25
1800
(816.4)
Red
1.22
(30.9)
CP-4-26
2400 (1088.6)
Purple
1.17
(29.7)
CP-4-27
3000 (1360.8)
Orange
1.06
(26.9)
CP-4-28
3600 (1632.9)
Green
1.02
(25.9)
CP-4-31
4400 (1995.8)
Gray
.83
(21.0)
CP-4-32
5200 (2358.7)
White
.74
(18.7)
CP-4-35
6000 (2721.6)
Gold
.70
(17.7)
COMPRESSOR MOUNTING
The compressors are mounted on four (4) isolator pads
(one under each compressor foot). (See Fig. 4). The
mounting bolts are not to be loosened or adjusted at
installation.
CHILLED LIQUID PIPING
GENERAL – When the unit has been located in its final
position, the unit liquid piping may be connected. Nor-
mal installation precautions should be observed in order
to receive maximum operating efficiencies. Piping should
be kept free of all foreign matter. All liquid cooler piping
must comply in all respects with local plumbing codes
and ordinances.
COMPRESSOR MOUNTING PAD