56
YORK INTERNATIONAL
PRINT KEYS
FIG. 20
OPERATING DATA PRINTOUT
26572A(D)
PRINT
KEYS
GENERAL
The PRINT keys allow the operator to obtain a remote
print-out of real-time system operating data and a print-
out of system data at the instant of the fault on the last
three faults which occurred on the chiller.
If a remote printer is not being used, or the desire is to
obtain data locally at the panel, the same keys allow
access to identical fault data. Identical and additional
real-time information is available by using a combination
of the PRINT keys and the other keys on the keypad.
An explanation of the use of the keys for remote printer
or local data retrieval will follow. An optional printer (Page
78) will be required for remote printout.
REMOTE PRINTOUT
Oper Data
The OPER DATA key allows the operator to remotely
obtain a printout of current system operating parame-
ters. When the key is pressed, a snapshot will be taken
of system operating conditions and panel programming
selections. This data will be temporarily stored in mem-
ory and transmission of this data will begin to the re-
mote printer. As the data is transmitted, it will be erased
from memory.
A sample printout is shown in Fig. 20.
History
The HISTORY key allows the operator to remotely ob-
tain a printout of information relating to the last 3 Safety
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SYSTEM STATUS
8:45AM 4/17/91
SYS 1
COMPRESSOR RUNNING
SYS 2
ANTI-COIN TIMER 13 SEC.
RETURN WATER TEMP
65.0 DEGF
LEAVING WATER TEMP
54.0 DEGF
LOW WATER CUTOUT
36.0 DEGF
SETPOINT TEMP
45.0 DEGF
OUTSIDE AIR TEMP
75.0 DEGF
LOW AMBIENT CUTOUT
10.0 DEGF
LOW PRESSURE CUTOUT
4 4 PSIG
LEAD SYSTEM
SYS 1
CONTROL TYPE
LCHWT
COOLING RANGE
45.0 TO 47.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
5 0 %FLA
SUCTION PRESSURE
6 1 PSIG
DISCHARGE PRESSURE
1 4 3 PSIG
OIL PRESSURE
7 5 PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
OFF
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
0 %FLA
SUCTION PRESSURE
6 1 PSIG
DISCHARGE PRESSURE
8 0 PSIG
OIL PRESSURE
1 PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
1
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
S M T W T F S
*=HOLIDAY
SUN
START=06:00AM
STOP=11:00AM
MON
START=06:00AM
STOP=11:00AM
TUE
START=06:00AM
STOP=11:00AM
WED
START=06:00AM
STOP=11:00AM
THU
START=06:00AM
STOP=11:00AM
FRI
START=06:00AM
STOP=11:00AM
SAT
START=06:00AM
STOP=11:00AM
HOL
START=00:00AM
STOP=11:00AM
OPER
DATA
HISTORY