SECTION 5 - COMMISSIONING
Remote or local
change over
Turn on power source
Initialize self-check
mechanism
(1~2 min)
Chilled / hot water,
cooling water pump start
Chilled / hot water
and cooling water pump
interlock ON?
Solution pump and
refrigerant pump start
Burner fan starts
Local start operation
Remote start operation
Air conditioning machine
and cooling tower fan
start
Abnormal warning
Remote
Local
No
(within 3 min.)
Yes
Time up
Temperature control
operation
Hold low
combustion
Ignition sequence
FIGURE 27 -
COOLING START DIAGRAM
FIGURE 28 -
COOLING STOP DIAGRAM
Stop Operation
Dilution operation starts
Combustion stops
Chilled water or
refrigerant temp.
low cut-out
Yes
Dilution time up
No
HT-Gen.
pressure low
No
Dilution operation
more than 30 min
No
No
Yes
Yes
Solution pump/
refrigerant pump
stop
Chilled/hot water
cooling water pump
stop
Stop
Dilution operation
time increases
Dilution
operation time
stops increasing
Solution and
refrigerant
pump stop
Solution and
refrigerant pump
continue
Yes
Air conditioning machine
and cooling tower fan
stop
Burner stops