SECTION 4 - TECHNICAL DATA
FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
4
MEASUREMENT
V
ALUE
15
Chilled/Hot water inlet temp.
12.0
°C
00083
0001~4000 unit, 1 unit=0.1°C
16
Chilled/Hot water outlet temp.
7.0
°C
00085
0001~4000 unit, 1 unit=0.1°C
17
Refrigerant temp. at evaporator
5.0
°C
00087
0001~4000 unit, 1 unit=0.1°C
18
Cooling water inlet temp.
32.0
°C
00089
0001~4000 unit, 1 unit=0.1°C
19
Cooling water outlet temp
37.0
°C
00091
0001~4000 unit, 1 unit=0.1°C
20
Absorber solution temp.
38.0
°C
00093
0001~4000 unit, 1 unit=0.1°C
21
High temperature generator
solution temp.
145.0
°C
00095
0001~4000 unit, 1 unit=0.1°C
22
Exhaust gas temp.
220.0
°C
00097
0001~4000 unit, 1 unit=0.1°C
23
High temperature generator
pressure
70.0
kPa
00099
0001~1100 unit, 1 unit=0.1 kPa
24
Motor opening rate
100.0
%
00101
0001~1100 unit, 1 unit=0.1%
25
High temperature generator
concentration
62.0
%
00103
0001~1100 unit, 1 unit=0.1%
26
Purge tank pressure
2.0
kPa
00105
0001~4000 unit, 1 unit=0.1 kPa
TABLE 24 -
WRITE COMMAND
ITEM
ADDRESS
CONTENT
1
Chiller-heater operation signal
02001
ON at CHILLER-HEATER OPERATION,
PULSE SIGNAL
2
Chiller-heater stop signal
02002
ON at CHILLER-HEATER STOP, PULSE
SIGNAL
3
Set point
00203
0050~1000 unit, 1 unit=0.1°C
TABLE 13
- READ COMMAND (CONT.)