![York EX Series Installation, Operation & Maintenance Instructions Manual Download Page 86](http://html2.mh-extra.com/html/york/ex-series/ex-series_installation-operation-and-maintenance-instructions-manual_3549149086.webp)
JOHNSON CONTROLS
86
FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
SECTION 5 - COMMISSIONING
JOHNSON CONTROLS
5
FORM 155.32-CL1
ISSUE DATE: 03/31/2017
DIRECT FIRED ABSORPTION CHILLER-HEATER COMMISSIONING DATA SHEET (1/3)
User:
Model:
MFG.No.:
User's machine code:
Insulation Resistance
Electric Power Supply
Standard: 5 MΩ or more (with 500 V meg
-
ger)
R-Gnd
S-Gnd
T-Gnd
Specification: AC
V /
Hz
Circuit breaker
MΩ
Standard: /- 10% of spec.
R-S
V
U-Gnd
V-Gnd
W-Gnd
R-T
V
Solution circulation pump
MΩ
S-T
V
Solution spray pump
MΩ
R-Gnd
V
Refrigerant pump
MΩ
S-Gnd
V
Purge pump
MΩ
T-Gnd
V
Thermal Relay Setting
Refrigerant Purity
Temperature Setting
Solution circulation pump
A
Standard: 1.040 (kg/L) or less
Cooling
Solution spray pump
A
Specific gravity
Set base temp.
°C
Refrigerant pump
A
Turbidity
Auto. stop temp
°C
Purge pump
A
Auto restart diff.
°C
Heating
Pump Discharge Pressure
Purge Amount
Set base temp.
°C
Solution circulation pump
MPa.G Standard: 4 cc/min or less
Auto. stop temp.
°C
Solution spray pump
MPa.G Purge tank
cc Auto. restart diff.
°C
Refrigerant pump
MPa.G Absorber
cc
NOTES:
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________