JOHNSON CONTROLS
31
FORM 155.32-ICOM1.EN.GB
ISSUE DATE: 10/13/2017
4
SECTION 4 - TECHNICAL DATA
This section includes technical information about
the unit, such as weight, dimensions, electrical data,
wiring, and sound data.
TABLE 4 -
TYPICAL OPERATIONAL RANGE
PARAMETER
ALLOWABLE RANGES
Chilled Water In
7 - 25°C
Chilled Water Out
4 - 16°C
Cooling Water In
20 - 37°C
Cooling Water Out
25 - 42°C
Natural Gas Inlet
Pressure
120 - 300 RT: 2 - 250 kPa(g)
360 - 1600 RT: 10 - 250 kPa(g)
The numbers shown in
are the
allowable ranges for each parameter. Not all combi-
nations are possible. Please check with your Johnson
Controls Service Center to see if your temperature dif-
ferential is possible.