SECTION 5 - COMMISSIONING
JOHNSON CONTROLS
7
FORM 155.32-CL1
ISSUE DATE: 03/31/2017
DIRECT FIRED ABSORPTION CHILLER-HEATER COMMISSIONING DATA SHEET (3/3)
User:
Model:
MFG.No.:
User's machine code:
Running Data
Date:
Measured by
Specification
Standard
:
:
:
Fuel
Output Valve
%
Control panel
Exhaust gas temperature
°C
Control panel
≤ 250°C
Fuel Consumption
Flow meter
chilled/hot
water
Inlet temperature
°C
Control panel
Outlet temperature
°C
Control panel
Inlet pressure
Pressure gauge
Outlet pressure
Pressure gauge
[3] Pressure drop
DPG or calculation
[4]
[1] Flow rate
FM or calculation
[2]
cooling
water
Inlet temperature
°C
Control panel
20.0~32.0°C
Outlet temperature
°C
Control panel
20.0~37.5°C
Inlet pressure
Pressure gauge
Outlet pressure
Pressure gauge
[7] Pressure drop
DPG or calculation
[8]
[5] Flow rate
FM or calculation
[6]
Absorption
cycle
HG pressure (gauge)
MPa.G
Compound gauge
≤ -0.003
MPa
HG pressure (sensor)
kPa.abs
Control panel
≤ 94.7 kPa
HG temperature
°C
Control panel
≤165°C
HG solution concentration
%
Control panel
Absorber temperature
°C
Control panel
Refrigerant temperature
°C
Control panel
Liquid
Level
HG
Level gauge
LG
Level gauge
Absorber
Level gauge
Evaporator (lower)
Level gauge
Evaporator (upper)
Level gauge
NOTES:
Operating hours________hours
Number of purge times________times
Fill out each specification pressure drop according to the factory inspection report (actual value).
If differential pressure gauge (DPG) is not available, calculate each pressure drop.
If flow meter (FM) is not available, calculate each flow rate as below.
[1] = [2] x √[3] / [4] [5] = [6] x √[3] / [4]
LD20020
Same
Height
Waterbox
OUT
P
P
IN