background image

CRANKCASE HEATER

The crankcase heaters must be energized at least 8 hours bef-
ore starting the compressor. To energize the crankcase heat-
ers, the main disconnect switch must be closed. During this 8
hour period, the system switch on the room thermostat must be
“OFF” to prevent the compressor from starting.

CAUTION: DO NOT ATTEMPT TO START THE COM-

PRESSOR WITHOUT AT LEAST 8 HOURS OF
CRANKCASE HEAT OR COMPRESSOR DAM-
AGE WILL OCCUR.

Make sure that the bottom of the compressor is warm to the
touch to prove crankcase heater operation.

PRE-START CHECK

Before starting the unit, complete the following check list:

1. Have sufficient clearances been provided?
2. Has all foreign matter been removed from the interior of the

unit (tools, construction or shipping materials, etc.)?

3. Have the outdoor fans been rotated manually to check for

free rotation?

4. Are all wiring connections tight?
5. Does the available power supply agree with the nameplate

data on the unit?

6. Have the fuses, disconnect switch and power wire been

sized properly?

7. Are all compressor hold-down nuts properly secured?
8. Are any refrigerant lines touching each other or any sheet

metal surface? Rubbing due to vibration could cause a re-
frigerant leak.

9. Are there any visible signs of a refrigerant leak, such as oil

residue?

10. Is any electrical wire laying against a hot refrigerant line?

Keep in mind that this unit has a reverse cycle and that dif-
ferent lines will be hot during the “HEAT” and “COOL” cy-
cles. Only two lines will remain cool for all cycles - the line
between the compressor and the accumulator and the line
between the accumulator and the reversing valve.

INITIAL START-UP

1. Supply power to the unit through the disconnect switch

prior to starting the compressor.

2. Move the system switch on the room thermostat to the

“COOL” position, and lower its set point to energize both
the compressor and the reversing valve. Cool air will be
supplied to the conditioned space.

3. Check the compressor amperage. It should not exceed the

RLA rating printed on the unit data plate or in Table 3 unless
the ambient temperature is above 105

°

F.

4. Move the system switch on the room thermostat to the

“HEAT” position, and increase the set point of the room
thermostat until heating is required. The compressor will
run, but the reversing valve will be de-energized. Warm air
will be supplied to the conditioned space.

5. Check the operation of the indoor unit per

Form 515.41-N4Y.

6. Check the entire system for refrigerant leaks.
7. Check for any abnormal noises and/or vibrations, and make

the necessary adjustments to correct (e.g. fan blade touching
shroud, refrigerant lines hitting on sheet metal, etc.)

8. After the unit has been operating for several minutes, shut

off the main power supply at the disconnect switch and in-
spect all factory wiring connections and bolted surfaces for
tightness.

SAFETY FEATURES

1. All outdoor fan motors have inherent protection with auto-

matic reset.

2. Every compressor is internally protected against excessive

current and temperature by a line break motor protector that is
mounted inside the compressor housing and is connected
between each winding and the common terminal.
This motor protector will interrupt power to the compressor
if any of the following overload conditions occur:

a. primary single phasing
b. locked rotor
c. compressor overload
d. insufficient motor cooling
This type of motor protection works even with the contactor
welded closed.

3. Every compressor is protected by crankcase heaters to

prevent refrigerant from accumulating in the crankcases of
the compressor during an “OFF” cycle.

4. Outdoor fan motors and the secondary of the control trans-

former are grounded.

5. A fusible plug on the top of the suction line accumulator

serves as a high temperature/high pressure relief device.

14

Unitary Products Group

035-16192-001-A-1001

SECURE OWNER'S APPROVAL:

When the system is functioning properly, secure the owner's approval. Show him the

location of all disconnect switches and the thermostat. Teach him how to start and stop the unit, how to adjust temperature

settings within the limitations of the system

START-UP

CAUTION:

DO NOT ATTEMPT TO START THE
COMPRESSOR WITHOUT AT LEAST
8 HOURS OF CRANKCASE HEAT
OR COMPRESSOR DAMAGE WILL
OCCUR.

MAINTENANCE

CLEANING

Do not allow dirt to accumulate on the outdoor coil. Clean the

coil with a brush or vacuum cleaner as often as necessary to

assure good system performance and efficient operation. If
the coil is extremely dirty, it may be necessary to use an in-

dustrial grade detergent and a hose to clean the fin surface.

LUBRICATION

The outdoor fan motors are equipped with factory lubricated
and sealed ball bearings. They do not require any mainte-
nance.

REPLACEMENT PARTS

Contact your local UPG Distribution Center for replacement
compressors, fan motors, controls, etc.

NOTICE TO OWNER

If a lockout occurs, check the indoor filters and the outdoor coil
before calling a serviceman. If the filters are dirty, clean or re-
place them. If there is an accumulation of snow, leaves or debris
blocking the outdoor air coil, remove the blockage. Reset the
thermostat and wait 5 minutes. If the unit doesn't start, call a
serviceman.

Summary of Contents for E1FB180

Page 1: ...cycle plus a check valve to provide the proper flow of refrigerant through the unit during both the cooling and heating cycles All controls are located in the front of the unit and are readily access...

Page 2: ...g Operation 11 Heating Operation 12 Defrost Cycle 12 Operation Below 0 F 13 Emergency Heat Operation 13 START UP CRANKCASE HEATER 10 Ton Unit Only 14 PRE START CHECK 14 INITIAL START UP 14 SAFETY FEAT...

Page 3: ...on re quirements GROUND LEVEL LOCATIONS The units must be installed on a substantial base that will not settle Any strain on the refrigerant lines may cause a refriger ant leak Aone piece concrete sla...

Page 4: ...he dis connect switch and the unit Refer to Figure 4 for the location of the power wire access opening through the front of the unit This opening will re quire a field supplied conduit fitting The fie...

Page 5: ...1 System 2 Power Supply Power Supply Maximum Fuse Size 1 Minimum Wire Size AWG 2 Maximum Wire Length feet 3 Minimum Disconnect Amps E1FB180A25 208 230 3 60 32 1 195 0 32 1 195 0 208 230 1 60 1 4 7 1...

Page 6: ...Bottom2 0 1 Units must be installed outdoors Overhanging structures or shrubs should not obstruct condenser air discharge 2 Adequate snow clearance must be provided if winter operation is expected Co...

Page 7: ...t be designed for the pressure drop due to both friction loss and vertical rise If the total pressure drop exceeds 40 psi some refrigerant may flash before it reaches the thermal expansion valve This...

Page 8: ...left on these surfaces may lead to a future system malfunction NOTE Use only copper tubing that has been especially cleaned and dehydrated for refrigerant use If the tub ing has been open for an exte...

Page 9: ...d EXTENDING THE SERVICE PORTS Refer to Fig 5 1 Loosen the screws that secure the service ports in shipping position 2 Push the service ports through the corner post 3 Tighten the screws to secure the...

Page 10: ...or the outdoor unit the indoor unit and the refrig erant lines using information in Tables 2 Physi cal Data and 6 Refrigerant Line Charge Using the charging procedures outlined above weigh the require...

Page 11: ...diagram COOLING OPERATION 1 The following controls will be energized through terminal O on the thermostat to put the system in the cooling mode Relays RY3 RY4 RY5 and RY6 2 If the fan switch on the t...

Page 12: ...hermostat will cycle the unit to satisfy the heating re quirements of the conditioned space 5 After the unit has shutdown from a heating cycle or a power interruption the anti short cycle feature of t...

Page 13: ...the room thermostat same as described under Item 8 of HEATING OPERA TION 2 The indoor section blower operation will be controlled by the first stage heating TH1 of the room thermostat if the fan switc...

Page 14: ...Check for any abnormal noises and or vibrations and make the necessary adjustments to correct e g fan blade touching shroud refrigerant lines hitting on sheet metal etc 8 After the unit has been oper...

Page 15: ...0 Suction Pressure psig Discharge Pressure psig 115 F 105 F 95 F 85 F 75 F ODDB 150 200 250 300 350 400 450 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 115 F 105 F 95 F 85 F 75 F ODDB...

Page 16: ...180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 10 HEATING MODE CHARGING CHART AT 6000 CFM EFB180A 50 100 150 200 250 300...

Page 17: ...B180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 12 HEATING MODE CHARGING CHART AT 6400 CFM EFB240A 50 100 150 200 250 30...

Page 18: ...EFB240A 50 100 150 200 250 300 350 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 14 HEATING MODE CHARGING CHART AT 7600 CFM EFB240A 50 100 150 200 250 300...

Page 19: ...NOTES Unitary Products Group 19 035 16192 001 A 1001...

Page 20: ...up 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2001 All Rights Reserved Code SBY 035 16192 001 A 1001 Supersedes...

Reviews: