background image

3.

Turn the stem in (or clockwise) between 1/4 and 1/2 turn to
open the access port.

As soon as some internal pressure is relieved, close the ac-

cess port. DO NOT remove the entire holding charge.

NOTE: The copper disc on the liquid connection will prevent

any internal pressure from being relieved through the
main port of the liquid line stop valve.

If the unit has already lost its holding charge, it should be

leak tested and the necessary repairs should be made. If the

unit has maintained its holding charge, you can assume that

it has no leaks and proceed with the installation.

CAUTION: Dry nitrogen should always be supplied through a

connection while it is being brazed or unbrazed be-
cause the temperature required to make or break a
brazed joint is sufficiently high to cause oxidation
of the copper unless an inert atmosphere is pro-
vided. The flow of nitrogen should be continued
until the joint has cooled.

WARNING The dry nitrogen must always be supplied through

a pressure regulating valve.

Before installing the liquid line between the outdoor and in-

door units, remove the copper disc from the liquid connection

on the outdoor unit per the following procedure:

1.

Make sure the refrigerant in the line has been recovered
and that the liquid service valve on the unit is front-seated
and closed. The valve stem should be turned to its maxi-
mum clockwise position.

2.

Drill a small hole through the disc before unbrazing it to per-
mit a flow of dry nitrogen through the connection while it is
being unbrazed.

WARNING: This hole is also required to prevent the internal

pressure from building up as the disc is being un-
brazed and from blowing the disc off.

This warning applies to any disc being removed
from a service valve, coil connection, etc.

3.

Remove the cap from the 1/4" access port on the liquid line
stop valve.

4.

Connect a supply of dry nitrogen to this access port.

5.

Unbraze the copper disc from the liquid connection while
maintaining a minimum flow of dry nitrogen through the
connection.

After the disc has been removed,

1.

Burnish the external surfaces of the liquid connection on
the outdoor unit and the end of the field-supplied piping be-
ing used for the liquid line.

NOTE: Clean surfaces are essential for a well brazed connec-

tion.

2. Carefully clean the internal surfaces of the above. Any par-

ticles left on these surfaces may lead to a future system
malfunction.

NOTE: Use only copper tubing that has been especially

cleaned and dehydrated for refrigerant use. If the tub-
ing has been open for an extended period of time, it
should be cleaned before being used.

The liquid line connections can now be brazed while maintain-
ing a minimum flow of dry nitrogen through the piping.

NOTE: A filter-drier is factory-mounted in the outdoor unit for

the heating cycle and in the indoor unit for the cooling
cycle.

Do NOT install another filter-drier in the field-supplied
liquid line because refrigerant will flow in both direc-
tions on a heat pump system.

Recover the holding charge of the indoor unit and then remove
the sealing caps or discs from both its liquid and vapor connec-
tions per the following procedure:

1. Make sure the refrigerant in the lines has been recovered,

then drill a small hole through both the liquid disc and the
vapor disc. If the holding charge has already been lost, the
coil should be leak-tested and the necessary repairs
should be made.

2. Move the dry nitrogen supply from the access port on the

liquid line service valve of the outdoor unit to the hole
through the vapor disc on the indoor unit.

3. Unbraze the coil's liquid line disc while maintaining a flow of

dry nitrogen across the connection and through the hole in
the liquid line disc.

8

Unitary Products Group

035-16192-001-A-1001

Refrigerant

Line

2

Line Size,

OD (In.)

Refrigerant Charge

(Lb/Ft)

Liquid

5/8

0.113

Vapor

1-1/8

0.013

1-3/8

1

Charges are based on 40

°

F suction temperature and 105

°

F liquid temperature.

2

Type “L” copper tubing.

TABLE 6 - REFRIGERANT LINE CHARGE

1

Use these line charges to adjust the system operating
charge when the refrigerant lines are more or less than the
25 feet listed in Table 2.

Model Designation

Nominal

Capacity

(Tons)

Refrigerant
Flow Rate

1

(Lbs./Min.)

Type L

Copper Tubing

(Inches O.D.)

Pressure Drop

3

Friction

2

(PSI/100 Ft.)

Vertical

Rise

(PSI/Ft.)

180

System 1

7-1/2

22.5

5/8

3.5

0.5

System 2

240

System 1

10

30.0

5/8

5.8

0.5

System 2

1

Based on Refrigerant-22 at the nominal capacity of the condensing unit, a liquid temperature of 105

°

F and a suction temperature of 40

°

F.

2

These friction losses do not include any allowances for a strainer, filter-drier, solenoid valve, isolation valve or fittings.

3

The total pressure drop of the liquid line for both friction and vertical rise must not exceed 40 PSI. If the pressure drop exceeds 40 PSI, the liquid refrigerant could flash before it reaches the

TABLE 5 - LIQUID LINES

Summary of Contents for E1FB180

Page 1: ...cycle plus a check valve to provide the proper flow of refrigerant through the unit during both the cooling and heating cycles All controls are located in the front of the unit and are readily access...

Page 2: ...g Operation 11 Heating Operation 12 Defrost Cycle 12 Operation Below 0 F 13 Emergency Heat Operation 13 START UP CRANKCASE HEATER 10 Ton Unit Only 14 PRE START CHECK 14 INITIAL START UP 14 SAFETY FEAT...

Page 3: ...on re quirements GROUND LEVEL LOCATIONS The units must be installed on a substantial base that will not settle Any strain on the refrigerant lines may cause a refriger ant leak Aone piece concrete sla...

Page 4: ...he dis connect switch and the unit Refer to Figure 4 for the location of the power wire access opening through the front of the unit This opening will re quire a field supplied conduit fitting The fie...

Page 5: ...1 System 2 Power Supply Power Supply Maximum Fuse Size 1 Minimum Wire Size AWG 2 Maximum Wire Length feet 3 Minimum Disconnect Amps E1FB180A25 208 230 3 60 32 1 195 0 32 1 195 0 208 230 1 60 1 4 7 1...

Page 6: ...Bottom2 0 1 Units must be installed outdoors Overhanging structures or shrubs should not obstruct condenser air discharge 2 Adequate snow clearance must be provided if winter operation is expected Co...

Page 7: ...t be designed for the pressure drop due to both friction loss and vertical rise If the total pressure drop exceeds 40 psi some refrigerant may flash before it reaches the thermal expansion valve This...

Page 8: ...left on these surfaces may lead to a future system malfunction NOTE Use only copper tubing that has been especially cleaned and dehydrated for refrigerant use If the tub ing has been open for an exte...

Page 9: ...d EXTENDING THE SERVICE PORTS Refer to Fig 5 1 Loosen the screws that secure the service ports in shipping position 2 Push the service ports through the corner post 3 Tighten the screws to secure the...

Page 10: ...or the outdoor unit the indoor unit and the refrig erant lines using information in Tables 2 Physi cal Data and 6 Refrigerant Line Charge Using the charging procedures outlined above weigh the require...

Page 11: ...diagram COOLING OPERATION 1 The following controls will be energized through terminal O on the thermostat to put the system in the cooling mode Relays RY3 RY4 RY5 and RY6 2 If the fan switch on the t...

Page 12: ...hermostat will cycle the unit to satisfy the heating re quirements of the conditioned space 5 After the unit has shutdown from a heating cycle or a power interruption the anti short cycle feature of t...

Page 13: ...the room thermostat same as described under Item 8 of HEATING OPERA TION 2 The indoor section blower operation will be controlled by the first stage heating TH1 of the room thermostat if the fan switc...

Page 14: ...Check for any abnormal noises and or vibrations and make the necessary adjustments to correct e g fan blade touching shroud refrigerant lines hitting on sheet metal etc 8 After the unit has been oper...

Page 15: ...0 Suction Pressure psig Discharge Pressure psig 115 F 105 F 95 F 85 F 75 F ODDB 150 200 250 300 350 400 450 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 115 F 105 F 95 F 85 F 75 F ODDB...

Page 16: ...180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 10 HEATING MODE CHARGING CHART AT 6000 CFM EFB180A 50 100 150 200 250 300...

Page 17: ...B180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 12 HEATING MODE CHARGING CHART AT 6400 CFM EFB240A 50 100 150 200 250 30...

Page 18: ...EFB240A 50 100 150 200 250 300 350 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 14 HEATING MODE CHARGING CHART AT 7600 CFM EFB240A 50 100 150 200 250 300...

Page 19: ...NOTES Unitary Products Group 19 035 16192 001 A 1001...

Page 20: ...up 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2001 All Rights Reserved Code SBY 035 16192 001 A 1001 Supersedes...

Reviews: