background image

LIMITATIONS

These units must be installed in accordance with all national
and local safety codes. If no local codes apply, installation must
conform with the appropriate national codes. See Table 1 for
unit application data. Units are designed to meet National
Safety Code Standards. If components are to be added to a unit
to meet local codes, they are to be installed at the dealer's
and/or the customer's expense.

LOCATION

Use the following guidelines to select a suitable location for
these units.

1. The outdoor units must be installed outside the building.

The outdoor fans are the propeller type and are not suitable
for use with duct work.

2. The outdoor and indoor units should be installed as close

together as possible and with a minimum number of bends
in the refrigerant piping. Refer to REFRIGERANT PIPING
for additional information.

3. The outdoor unit should not be installed beneath windows

or between structures where normal operating sounds may
be objectionable.

WARNING: The outdoor unit should not be installed in an area

where mud and/or ice could cause personal injury.
Remember that condensate will drip from the un-
derside of the unit coils during heat and defrost cy-
cles and that this condensate will freeze when the
temperature of the outdoor air is below 32

°

F.

4. All units require certain clearances for proper operation and

service.

On either rooftop or ground level installations, rubber padding
can be applied between the base rails and their supports to
lessen any transmission of vibration.

ROOF-TOP LOCATIONS

Be careful not to damage the roof. Consult the building contrac-
tor or architect if the roof is bonded. Choose a location with ade-
quate structural strength to support the unit.

The unit must be mounted on solid level supports. The sup-
ports can be channel iron beams or wooden beams treated to
reduce deterioration.

A minimum of two (2) beams are required to support each unit.
The beams should: (1) Be positioned perpendicular to the roof
joists. (2) Extend beyond the dimensions of the unit to distribute
the load on the roof, (3) Be capable of adequately supporting
the entire unit weight. Refer to Figure 1 and Table 2 for load dis-
tribution and weights.

These beams can usually be set directly on the roof. Flashing is
not required.

NOTE: On bonded roofs, check for special installation re-

quirements.

GROUND LEVEL LOCATIONS

The units must be installed on a substantial base that will not
settle. Any strain on the refrigerant lines may cause a refriger-
ant leak. A one-piece concrete slab with footers that extend be-
low the frost line is recommended. The slab should not be tied
to the building foundation because noise and vibration will tele-
graph.

A unit can also be supported by concrete piers. These piers
should: (1) extend below the frost line, (2) be located under the
unit's four corners and (3) be sized to carry the entire unit
weight. Refer to Figure 1 and Table 2 for the center of gravity
and unit weight.

A gravel bed or some other means of handling the condensate
that will drop from the underside of the unit coil during the heat-
ing and defrost cycles may have to be provided.

CAUTION: Care should be taken to protect the unit from

tampering and unauthorized persons from injury.
Screws on access panels will prevent casual
tampering. Additional safety precautions such as
fences around the unit or locking devices on the
panels may  be advisable. Check local authori-
ties for safety regulations.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove any pack-
aging until the unit is near the place of installation.

Rig the unit by attaching chain or cable slings with hooks to the
round lifting holes provided in the base rails.

CAUTION: Spreaders, longer than the largest dimension

across the unit, MUST be used across the top of
the unit.  See Figure 2.

WARNING: BEFORE LIFTING A UNIT, MAKE SURE THAT

ITS WEIGHT IS DISTRIBUTED EQUALLY ON
THE CABLES SO THAT IT WILL LIFT EVENLY.

Units may also be moved or lifted with a fork-lift from the front,
rear or the compressor end only through the slotted openings
provided in the base rails.

Unitary Products Group

3

035-16192-001-A-1001

INSTALLATION

BACK

(COIL END)

FRONT

A

39 - 7/8

APPROXIMATE

CENTER OF GRAVITY

B

76 - 7/8

FIG. 1 - CENTER OF GRAVITY

APPLICATION LIMITATIONS

MIN

MAX

Voltage Variation (208/230-3-60) - Volts

2

187

253

Voltage Variation (460-3-60) - Volts

2

414

506

Ambient Air on Outdoor Coil (Cooling Cycle) - °F

45

115

Ambient Air on Indoor Coil (Cooling Cycle) - °F

68

86

Ambient Air on Outdoor Coil (Heating Cycle) - °F

0

1

70

Ambient Air on Indoor Coil (Heating Cycle) - °F

60

80

TABLE 1 - UNIT APPLICATION DATA

1

Rated in accordance with ARI Standard 110, utilization range “A”.

2

Below 0 °F, the control circuit will lock out the compressor and allow the

electric heat accessory to cycle at its standby capacity.

Unit

Dim. (in.)

A

B

15 Ton

16

38

20 Ton

16

38

Summary of Contents for E1FB180

Page 1: ...cycle plus a check valve to provide the proper flow of refrigerant through the unit during both the cooling and heating cycles All controls are located in the front of the unit and are readily access...

Page 2: ...g Operation 11 Heating Operation 12 Defrost Cycle 12 Operation Below 0 F 13 Emergency Heat Operation 13 START UP CRANKCASE HEATER 10 Ton Unit Only 14 PRE START CHECK 14 INITIAL START UP 14 SAFETY FEAT...

Page 3: ...on re quirements GROUND LEVEL LOCATIONS The units must be installed on a substantial base that will not settle Any strain on the refrigerant lines may cause a refriger ant leak Aone piece concrete sla...

Page 4: ...he dis connect switch and the unit Refer to Figure 4 for the location of the power wire access opening through the front of the unit This opening will re quire a field supplied conduit fitting The fie...

Page 5: ...1 System 2 Power Supply Power Supply Maximum Fuse Size 1 Minimum Wire Size AWG 2 Maximum Wire Length feet 3 Minimum Disconnect Amps E1FB180A25 208 230 3 60 32 1 195 0 32 1 195 0 208 230 1 60 1 4 7 1...

Page 6: ...Bottom2 0 1 Units must be installed outdoors Overhanging structures or shrubs should not obstruct condenser air discharge 2 Adequate snow clearance must be provided if winter operation is expected Co...

Page 7: ...t be designed for the pressure drop due to both friction loss and vertical rise If the total pressure drop exceeds 40 psi some refrigerant may flash before it reaches the thermal expansion valve This...

Page 8: ...left on these surfaces may lead to a future system malfunction NOTE Use only copper tubing that has been especially cleaned and dehydrated for refrigerant use If the tub ing has been open for an exte...

Page 9: ...d EXTENDING THE SERVICE PORTS Refer to Fig 5 1 Loosen the screws that secure the service ports in shipping position 2 Push the service ports through the corner post 3 Tighten the screws to secure the...

Page 10: ...or the outdoor unit the indoor unit and the refrig erant lines using information in Tables 2 Physi cal Data and 6 Refrigerant Line Charge Using the charging procedures outlined above weigh the require...

Page 11: ...diagram COOLING OPERATION 1 The following controls will be energized through terminal O on the thermostat to put the system in the cooling mode Relays RY3 RY4 RY5 and RY6 2 If the fan switch on the t...

Page 12: ...hermostat will cycle the unit to satisfy the heating re quirements of the conditioned space 5 After the unit has shutdown from a heating cycle or a power interruption the anti short cycle feature of t...

Page 13: ...the room thermostat same as described under Item 8 of HEATING OPERA TION 2 The indoor section blower operation will be controlled by the first stage heating TH1 of the room thermostat if the fan switc...

Page 14: ...Check for any abnormal noises and or vibrations and make the necessary adjustments to correct e g fan blade touching shroud refrigerant lines hitting on sheet metal etc 8 After the unit has been oper...

Page 15: ...0 Suction Pressure psig Discharge Pressure psig 115 F 105 F 95 F 85 F 75 F ODDB 150 200 250 300 350 400 450 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 115 F 105 F 95 F 85 F 75 F ODDB...

Page 16: ...180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 10 HEATING MODE CHARGING CHART AT 6000 CFM EFB180A 50 100 150 200 250 300...

Page 17: ...B180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 12 HEATING MODE CHARGING CHART AT 6400 CFM EFB240A 50 100 150 200 250 30...

Page 18: ...EFB240A 50 100 150 200 250 300 350 30 40 50 60 70 80 90 Suction Pressure psig Discharge Pressure psig 80 F 70 F 60 F IDDB FIG 14 HEATING MODE CHARGING CHART AT 7600 CFM EFB240A 50 100 150 200 250 300...

Page 19: ...NOTES Unitary Products Group 19 035 16192 001 A 1001...

Page 20: ...up 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2001 All Rights Reserved Code SBY 035 16192 001 A 1001 Supersedes...

Reviews: